3.8 Output Set Up Group

Introduction

This group deals with various output types in the controller, the Digital Output Status and
the Current Output operation.

ATTENTION

The Tuning Group is automatically configured to have two PID sets

when a Duplex Control Algorithm is selected.

Function Prompts

Table 3-8 OUTPUT Group (Numeric Code 500) Function Prompts

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

OUTALG

501

The OUTPUT ALGORITHM lets you select
the type of output you want. Not applicable
with Control algorithm prompt TPSC
(Three Position Step Control).

Selections are hardware dependent. For
example, if the controller does not have a
current output, then none of the prompts for
Output Algorithms that need a current output
will appear. Likewise, if the controller does
not have a relay output, then none of the
prompts that need a relay output will appear.

ATTENTION For all Duplex Output forms,
PID heat parameters apply for controller
output greater than 50 %; PID cool
parameters apply for controller output less
than 50 %.

RLY

0

TIME SIMPLEX—This output algorithm uses
Digital Output 1 for Time Proportional
Control. The output is updated per the Loop
sampling rate selection. Time Proportional
Output has a resolution of 4.44 msec. Cycle
Time is adjustable from 1 to 120 seconds.

RLY2

1

TIME SIMPLEX—This output algorithm uses
Digital Output 2 for Time Proportional
Control. The output is updated per the Loop
sampling rate selection. Time Proportional
Output has a resolution of 4.44 msec. Cycle
Time is adjustable from 1 to 120 seconds.