Honeywell UDC2500 User Manual

Page 125

Advertising
background image

Monitoring and Operating the Controller

4/07

UDC2500 Universal Digital Controller Product Manual

111

Set up Procedure

Use the following procedure (Table 4-18) to:

• select two sets,
• set the switch-over value,
• set tuning constant value for each set.

Table 4-18 Set Up Procedure

Step

Operation

Press

Result

1

Select Control

Set-up Group

Setup

Setup

Until you see:
Upper Display
= SET

Lower Display = CONTRL

2

Select PID SETS

Function

Function

Function

Until you see:
Upper Display = (available selections)
Lower Display = PID SETS

3

Select PID SETS

Function

or

To select the type of function. Available selections are:

ONE—1 set of constants
2 KBD—2 sets, keyboard selectable
2 PR—2 sets, auto switch at PV value
2 SP—2 sets, auto switch at SP value

4

Set Tuning

Values for Each

Set

Function

Function

Function

Refer to “TUNING” Set up group, subsection 3.4 and set the
following tuning parameters:

PB or GAIN*
RATE T*
I MIN or I RPM*
CYCT1 or CTIX3*
PB2 or GAIN2**
RATE 2T**
I2MIN or I2RPM**
CYC2T2 or CT2X3**

*PIDSET1 will be used when PV or SP, whichever is
selected, is greater than the switchover value.

**PIDSET2 will be used when PV or SP, whichever is
selected, is less than the switchover value.

5

Set Switchover

Value for 2PR or

2SP Selection

Function

Function

Function

Until you see:
Upper Display
= (the switchover value)

Lower Display = SW VAL

or

To select the switchover value in the upper display.