Figure 2-14 – Honeywell UDC2500 User Manual

Page 42

Advertising
background image

Installation

28

UDC2500 Universal Digital Controller Product Manual

4/07

20

21

5

6

Control Relay #1

Motor

Power

Supply

Close (CCW)

Open (CW)

Control Relay #2

Alarm #2 is not available with this configuration.

1

L1/Hot

L2/N

2

2

1

Electromechanical Relays are rated at 5 amps at 120 Vac or 240 Vac
or 24 Vdc. Solid State Relays are rated at 1 Amp at 25

°C and

derated linearly to 0.5 Amps at 55

°C. Customer should size fuses

accordingly. Use Fast Blo fuses only.

Figure 2-13 Three Position Step Control Connections w/o Dual Relay

Option

19

20
21

Motor

Power

Supply

Close (CCW)

Open (CW)

Control
Relay #1

Control
Relay #2

L2/N

L1/Hot

Alarm #2 is available with with this configuration.

2 Dual Electromechanical relays are rated at 2 Amps @120 Vac or 240 Vac or

30 Vdc. Customer should size fuses accordingly. Use Fast Blo fuses only.

2

1

19

20
21

Motor

Power

Supply

Close (CCW)

Open (CW)

Control
Relay #1

Control
Relay #2

L2/N

L1/Hot

Alarm #2 is available with with this configuration.

2 Dual Electromechanical relays are rated at 2 Amps @120 Vac or 240 Vac or

30 Vdc. Customer should size fuses accordingly. Use Fast Blo fuses only.

2

1

Figure 2-14 Three Position Step Control Connections with Dual Relay

Option

Advertising