Modbus Read, Write and Override Parameters plus Exception Codes

214

UDC2500 Universal Digital Controller Product Manual

4/07

10.7.11 Alarms

Table 10-19 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Alarms.

Table 10-19 Set-up Group – Alarms

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Alarm 1 Setpoint 1
Value

0009

009

FP

R/W

Within the range of

selected parameter or PV
span for deviation alarm

Alarm 1 Setpoint 2
Value

000A

010

FP

R/W

Within the range of

selected parameter or PV
span for deviation alarm

Alarm 2 Setpoint 1
Value

000B

011

FP

R/W

Within the range of

selected parameter or PV
span for deviation alarm

Alarm 2 Setpoint 2
Value

000C

012

FP

R/W

Within the range of

selected parameter or PV
span for deviation alarm

Alarm 1 Setpoint 1
Type

008C 140

INT R/W

0 = None
1 = Input 1
2 = Input 2
3 = PV
4 = Deviation
5 = Output
6 = Alarm on Shed
7 = SP Event On
8 = SP Event Off
9 = Manual
10 = Remote Setpoint
11 = Failsafe
12 = PV Rate of Change
13 = Alarm on Digital

Input 1

14 = Alarm on Digital

Input 2

15 = Loop Break
16 = Deviation based upon

SP2

17 = T/C Warning
18 = T/C Fail