Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

207

10.7.7 Input

2

Table 10-15 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Input 2.

Table 10-15 Set-up Group – Input 2

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Input 2 Type

00AA 170

INT

R/W

0 = Disable
1 to 25 Unused
26 = 0-20 mA
27 = 4-20 mA
28 to 30 = Unused
31 = 0-5 Vdc
32 = 1-5 Vdc
33 = Unused
34 = Unused
35 = 0 – 2 Vdc

ATTENTION

Changing the Input Type will result in the loss of Field Calibration
values and will restore the Factory Calibration values.