Input Calibration

144

UDC2500 Universal Digital Controller Product Manual

4/07

5.5 Input 1 Calibration Procedure

Preliminary Steps

• Apply power and allow the controller to warm up for 30 minutes before you calibrate.
• Please read Subsection 5.4 – Input 1 Set Up Wiring before beginning the procedure.
Make sure you have LOCK set to NONE. See Subsection 3.4 - Tuning Set Up

Group.

See Table 5-1 for Voltage vs. Resistance equivalents or 0 % and 100 % range values.

CAUTION

For linear inputs, avoid step changes in inputs. Vary smoothly from initial value to final 100 % value.

Procedure

The calibration procedure for Input #1 is listed in Table 5-10. The numeric codes are also
listed.

Table 5-10 Input 1 Calibration Procedure (Numeric Code 10000)

Step

Operation

Press

Result

1

Enter Calibration
Mode

Setup

Setup

until you see

Upper Display

= CAL (

- - - -

)

Lower Display

= INPUT1 (10000)

Function

Function

Function

You will see:

Upper Display

= DIS ( 0 )

Lower Display

= CALIN1 (10001)

The calibration sequence is enabled and you will see:

Upper Display

= BEGN ( 1 )

Lower Display

= CALIN1 (10001)

At the completion of the sequence, the selection
automatically reverts to disable.

2

Calibrate 0 %

Function

Function

Function

You will see:

Upper Display

= APLY ( 2 )

Lower Display

= IN1ZRO (10002)

• Adjust your calibration device to an output signal equal

to the 0 % range value for your particular input sensor.
See Table 5-1 for Voltage, Degrees, or Resistance
equivalents for 0 % range values.

• Wait 15 seconds, then go to the next step.