Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

205

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Input 1
Transmitter
Characterization

00A9 169

INT

R/W

0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = R TC
14 = S TC
15 = T TC H
16 = T TC L
17 = W TC H
18 = W TC L
19 = 100 PT RTD
20 = 100 PT LO RTD
21 = 200 PT RTD
22 = 500 PT RTD
23 = Radiamatic RH
24 = Radiamatic RI
25 = Linear
26 = Square Root

Input 1 High
Range Value

001D

029

FP

R/W

–999. to 9999. Engineering
Units (Linear types only)

Input 1 Low
Range Value

001E

030

FP

R/W

–999 to 9999. Engineering
Units (Linear types only)

Input 1 Ratio

006A

106

FP

R/W

–20.00 to 20.00

Input 1 Bias

006B

107

FP

R/W

–999 to 9999. Engineering
Units

Input 1 Filter

002A

042

FP

R/W

0 to 120 seconds