Output Calibration

4/07

UDC2500 Universal Digital Controller Product Manual

153

Procedure

The procedure for calibrating the Current Output is listed in Table 6-2. The numeric
codes are also listed. Make sure LOCK in the Tuning Set Up group is set to NONE.
(See Subsection 3.4 – Tuning Set Up Group.)

Table 6-2 Current Output Calibration Procedure

(Numeric Code 30000)

Step

Operation

Press

Result

1

Enter Calibration
Mode

Setup

Setup

until you see

Upper Display

= CAL (

- - - -

)

Lower Display

= CURENT (30000)

2

Calibrate 0 %

Function

Function

Function

You will see:

Upper Display

=

A Value

Lower Display

= ZROVAL (30001)

or

Until the desired 0 % output is read on the milliammeter,
use the values shown below depending on the action of
your controller. Normally, this will be the setting that
produces 4 mA.

3

Calibrate 100 %

Function

Function

Function

This stores the 0 % value and
you will see:

Upper Display

=

A Value

Lower Display

= SPNVAL (30002)

or

Until the desired 100 % output is read on the milliammeter,
use the values shown below depending on the action of
your controller. Normally, this will be the setting that
produces 20 mA.

4

Function

Function

Function

The controller stores the span value.

Exit the
Calibration Mode

Lower

Display

Lower

Display

Lower

Display

To exit the calibration mode.