8 restoring factory configuration – Honeywell UDC2500 User Manual

Page 188

Advertising
background image

Troubleshooting/Service

174

UDC2500 Universal Digital Controller Product Manual

4/07

7.8 Restoring Factory Configuration

Introduction

This procedure restores the configuration of the instrument back to the Factory Settings
per Section 3.17.

ATTENTION: Restoring the factory configuration overwrites all user-entered
configuration changes. This procedure cannot be undone, it is a one-way process.

Table 7-15 explains how to restore Factory Configuration.

Table 7-15 Restoring Factory Configuration

Step

What to do

1

Turn off the power to the instrument for at least five seconds.

2

Turn the power back on and simultaneously press the “FUNCTION” and

keys. This must be done while “TEST DONE” is being displayed.

3

If step 2 was performed correctly, the instrument will now display “UDC”
[Upper] “UPDATE” [Lower].

4

Press the FUNCTION Key. The instrument will now display “DIS” [Upper]
“RESTORE” [Lower].

5

Press the

key. The instrument will now display “CFG” [Upper]

“RESTORE” [Lower].

6

Press the FUNCTION Key. The instrument will now display “DOIN”
“RESTORE”

7

When the instrument finishes the restore operation, it automatically resets
itself and restarts in the product mode. The instrument configuration will
now be the same as it was when the instrument left the factory and all user-
entered configurations since that time have been overwritten.

Advertising