9.4 Function Code 21 (15h) - Write Configuration Reference Data

Introduction

Function Code 21 (15 Hex) is used in this instrument to allow writes of integer and
floating point values to the configuration database and override values.

The configuration database of this instrument is located in EEROM. The override values
are stored in RAM.

Integer format is used to write to “Digital” configuration items. Floating Point format is
used to write to “Analog” configuration items as defined by the configuration ID tags.

Write Restrictions

Care should be taken not to exceed the 100,000 write limit of the EEROM.

Request and Response Formats

The Request and Response formats for Function code 21 (15 Hex) are shown below.
Details for each block reference follow.

Request Message Format

Slave

Address

Byte

Count

Function
Code 15

Reference

Type

File

Number

Register

Count

Register
Address

CRC
Data

CRC
Data

Data

Data

Data

Data

File

Number

Response Message Format (echo back of request)

Slave

Address

Byte

Count

Function
Code 15

Reference

Type

File

Number

Register

Count

Register
Address

CRC
Data

CRC
Data

Data

Data

Data

Data

File

Number

The register address is interpreted as the tag ID configuration number.

For Infrared Transactions, add three BOFs (C0hex) at the beginning of each message and
one EOF (FFhex) at the end of each message.

Reference Type Definitions

The Reference Type definition is always 06.
See examples in Subsection 9.4.1