Configuration

4/07

UDC2500 Universal Digital Controller Product Manual

41

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeri

c Code

English

Numeric

Code

Parameter

Definition

EUHRDN 206 0 to 9999 in

Engineering units
per hour

RATE DOWN—Rate down value. When
making a setpoint change, this is the rate at
which the controller will change from the
original setpoint down to the new one. The
ramping (current) setpoint can be viewed as
SPn in the lower display.

Entering a 0 will imply an immediate change
in Setpoint (i.e., no rate applies).

SPPROG
(optional
feature)

SP Ramp
must be
disabled for
SP Program
prompts to
appear. If
SP Rate is
enabled, it
does not
operate
while an SP
Program is
running.

207

DIS
ENAB

0
1

SETPOINT RAMP/SOAK PROGRAM
Available only with controllers that contain
this option.

SP RAMP must be disabled.

DISABLE—Disables setpoint programming.
ENABLE—Enables setpoint programming.

ATTENTION Detailed information for the
prompts for SP Programming may be found
in Section 4.21 – Setpoint Programming. The
listing below is only for reference purposes.

STRSEG 208 1 to 11

Start Segment Number

ENDSEG 209

2 to 12 (always end in
a soak segment)
SOK 2
SOK 4
SOK 6
SOK 8
SOK 10
SOK 12

2
4
6
8

10
12

End Segment Number

RPUNIT 210

TIME
EU-M
EU-H

0
1
2

Engineering Units for Ramp Segments

TIME in hours:minutes
RATE in Enineering units per minute
RATE in Enineering units per hour

RECYCL 211 0 to 100 recycles

Number of Program Recycles

SOKDEV 212 0 to 100

Guaranteed Soak Deviation Value

PG END

213

LAST (Hold at last
SP) FSAF (Manual
mode/failsafe)

0
1

Program Termination State