Figure 2-15 and figure 2-16, Connect shield to ground at one end only – Honeywell UDC2500 User Manual

Page 43

Advertising
background image

Installation

4/07

UDC2500 Universal Digital Controller Product Manual

29

1 Do not run the communications lines in the same conduit as AC power.

D–

D+

COMMUNICATION MASTER

D+ (B) SHLD

D– (A)

120 OHMS

TO OTHER

COMMUNICATION

CONTROLLERS

D+

D–

120 OHMS ON LAST LEG

16 SHLD

17 D+ (B)

18 D– (A)

Connect shield
to ground at one
end only.

SHLD

2 Use shielded twisted pair cables (Belden 9271 Twinax or equivalent).

2

1

Figure 2-15 RS-422/485 Communications Option Connections

1 Do not run the communications lines in the same conduit as AC

power. Correct connections may require the use of an Ethernet
cross-over cable.

COMMUNIC

ATION MASTER

OR SWITCH

RXD+

SHLD

16 RXD-

17 TXD+

18 TXD-

14 SHLD

15 RXD+

RXD- TXD+

TXD-

1

2

Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.

2

3

Use Switch rather than Hub to maximize performance.

3

1 Do not run the communications lines in the same conduit as AC

power. Correct connections may require the use of an Ethernet
cross-over cable.

COMMUNIC

ATION MASTER

OR SWITCH

TXD–

SHLD

16 RXD –

17 TXD +

18 TXD –

14 SHLD

15 RXD +

TXD+ RXD– RXD+

1

2

Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.

2

3

Use Switch rather than Hub to maximize performance.

3

3

1 Do not run the communications lines in the same conduit as AC

power. Correct connections may require the use of an Ethernet
cross-over cable.

COMMUNIC

ATION MASTER

OR SWITCH

RXD+

SHLD

16 RXD-

17 TXD+

18 TXD-

14 SHLD

15 RXD+

RXD- TXD+

TXD-

1

2

Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.

2

3

Use Switch rather than Hub to maximize performance.

3

3

1 Do not run the communications lines in the same conduit as AC

power. Correct connections may require the use of an Ethernet
cross-over cable.

COMMUNIC

ATION MASTER

OR SWITCH

TXD–

SHLD

16 RXD –

17 TXD +

18 TXD –

14 SHLD

15 RXD +

TXD+ RXD– RXD+

1

2

Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.

2

3

Use Switch rather than Hub to maximize performance.

3

3

3

3

Figure 2-16 Ethernet Communications Option Connections

Figure 2-16 and Table 2-7 shows how to connect a UDC to a MDI Compliant Hub or
Switch utilizing a straight-through cable or for connecting a UDC to a PC utilizing a
crossover cable.