Output Calibration

4/07

UDC2500 Universal Digital Controller Product Manual

155

Procedure

The procedure for calibrating the auxiliary output is listed in Table 6-4. The numeric
codes are also listed.

Make sure “LOCK” in the Tuning Set Up group is set to “NONE” (see Subsection 3.4).

Table 6-4 Auxiliary Output Calibration Procedure

(Numeric Code 50000)

Step

Operation

Press

Result

1

Enter Calibration
Mode

Setup

Setup

until you see

Upper Display

= CAL (

- - - -

)

Lower Display

= AUXOUT (50000)

2

Calibrate 0 %

Function

Function

Function

You will see:

Upper Display

= A Value

Lower Display

= ZROVAL (50001)

or

until the desired 0 % output is read on the milliammeter,
use the values shown below depending on the action of
your controller. Normally, this will be the setting that
produces 4 mA.

3

Calibrate 100 %

Function

Function

Function

To store the 0 % value you will see:

Upper Display

= A Value

Lower Display

= SPNVAL (50002)

or

until the desired 100 % output is read on the milliammeter. .
Normally, this will be the setting that produces 20 mA.

4

Function

Function

Function

The controller stores the span value.

Exit the
Calibration Mode

Lower

Display

Lower

Display

Lower

Display

To exit the calibration mode.