Items to be checked, Mx100, Mw100 – Yokogawa PC-Based MX100 User Manual

Page 71

Advertising
background image

2-42

SM MX100-01E

Items to Be Checked

Confirm that all channels under test satisfy the specifications in the table below.
Also confirm that the output from channels not under test meet the criteria for 0 V in the
table below.

<MX100>

Voltage Output Criteria

Setting

Standard Value

Specification

-10 V (20000)

-10 V

±20 mV

0 V (0)

0 V

+5 V (10000)

+5 V

+10 V (20000)

+10 V

Current Output Criteria

Setting

Standard Value

Specification

+1 mA (500)

1 mA

±40A

+10 mA (5000)

10 mA

+20 mA (10000)

20 mA

+Over (20000)

22 mA or more

22 mA or more

The parentheses ( ) indicate the count value when entering settings with the MX100/
DARWIN API.

<MW100>

Voltage output criteria

Setting

Standard Value

Specification

-10 V (-10000)

-10 V

±20 mV

0 V

0 V

+5 V (5000)

+5 V

+10 V (10000)

+10 V

Current Output Criteria

Setting

Standard Value

Specification

+1 mA (1000)

1 mA

±40A

+10 mA (10000)

10 mA

+20 mA (20000)

20 mA

+Over (25000)

22 mA or more

22 mA or more

2.9 Tests of the 8-CH Analog Output Module