4 peak value test – Yokogawa PC-Based MX100 User Manual

Page 74

Advertising
background image

2-45

SM MX100-01E

Testing

1

2

3

4

5

6

7

2.10.3 ID Check

This test confirms whether the module is correctly identified when module information is
obtained from the MX100, MW100, or equivalent.
(If the OFF/ON cycle is not performed on the MX100, MW100, or equivalent, the ID
information is not updated. )

2.10.4 Peak Value Test

Wire the units as in the figure below, enter all settings (PWM output settings), then
confirm that the criteria are met.
Use an external power supply of 5 V, and load resistance of 5 Ω.

The wiring diagram in the figure below is an example of measurement on CH5. Actual
measurment should be performed on all channels.

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15

DC

Power

supply

+
-

DMM +

-

5V

V+

-

CH5

V+

-

CH6

V+

-

CH7

V+

-

CH8

+
-

Vext

+
-

Vext

V+

-

CH4

V+

-

CH3

V+

-

CH2

V+

-

CH1

Peak value check wiring diagram

PWM Outupt Settings

<MX100 Settings>
Connect to the PC, then enter the following settings using the MX100 standard software.
When using the MX100/DARWIN API for settings, enter settings that are equivalent to
the following.

Item

Setting

Remarks

Select output or no output Enabled
Select the source action

User output

Span

Need not specify

Output upon power ON

Preset value

Sets the output at power ON as a preset value.

Output upon error

Preset value

Sets the output upon error as a preset value.

Preset value

0.000 %

Sets 0% duty.

Pulse interval

10 ms

Sets the pulse interval to 10 ms.

Other settings

Not required

2.10 8-CH, Medium-Speed PWM Output Module

Advertising