2.10.8 Overcurrent Protection Circuit Operation Test

Wire the units as in the figure below, enter all settings (PWM output settings), then
confirm that the criteria are met.
The wiring diagram shows an example of wiring CH5. Actual measurment should be
performed on all channels.
Use an external power supply of 5 V or 12 V, and load resistance of 5 Ω.

Caution

For this test, set an output of 100.000% on each channel under test, and 0.000%
for all other channels. With other tests, the fuses in the internal circuitry can blow
if multiple channels are turned ON at the same time.

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15

+
-

100Ω

Counter +

-

5V

V+

-

5Ch

V+

-

6Ch

V+

-

7Ch

V+

-

8Ch

+
-

Vext

+
-

Vext

V+

-

4Ch

V+

-

3Ch

V+

-

2Ch

V+

-

1Ch

Puls interval check and puls duty check wiring diagram

DC

Power

supply

PWM Outupt Settings

<MX100 Settings>
Connect to the PC, then enter the following settings using the MX100 standard software.
When using the MX100/DARWIN API for settings, enter settings that are equivalent to
the following.

Item

Setting

Remarks

Enable/disable

Enabled

Action

User output

Span

Need not specify

Output upon power ON

Preset value

Sets the output at power ON as a preset value.

Output upon error

Preset value

Sets the output upon error as a preset value.

Preset value

0.000 %

Sets 0% duty.

Pulse interval

10 ms

Other settings

Not required