2-51

SM MX100-01E

Testing

1

2

3

4

5

6

7

<MW100 Settings>

Item

Setting

Remarks

Output Type

PWM

Output method

COM

Command output

Output range

1 ms

Span

Need not specify

Pulse interval

10

Preset value

0.000%

Reference channel

Not required

Output Operation Setting

Item

Setting

Power ON

PRESET

Error occurence

PRESET

Criteria (for the MX100 and MW100)

Change the settings following the steps in the table below, then confirm that the results
satisfy the criteria for voltage.

Step

External Power Supply PWM Output Setting

Voltage Criterion

1

5 V

100.000 %

3.8 V or more

2

12 V

100.000 %

0.04 V or less

3

5 V

100.000 %

0.04 V or less

4

OFF

100.000 %

5

5 V

100.000 %

3.8 V or more