Operating limits, Eseer calculations, Deltachill ™ chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 10

Advertising
background image

DELTACHILL

Chillers

10

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Operating Limits

(For 100% Water)

Unit with Electronic Fan Speed HP Control (-20°C)

Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C

Refer to

Performance Data

– Capacity Data

Minimum Leaving Water Temperature °C

+5°C and+6°C (DCC and DCF respectively)

Maximum Return Water Temperature °C

+18°C and+20°C (DCC and DCF respectively)

1

Temperatures lower than those stated can be obtained with the addition of glycol.

2

For conditions outside those quoted, please refer to Airedale.

ESEER Calculations

The quoted EER figures cover the performance of the unit ONLY at the standard rating
conditions of 7/12°C water, 35°C ambient. The ESEER calculation method has been
developed by Eurovent to give a single value that is a realistic indication of the efficiency
of the Chiller across the year round range of operation.

The ESEER value is calculated from the unit’s performance at 20, 25, 30 and 35°C
ambient temperatures for all loading stages, and with a fixed 7°C supply temperature. All
calculations assume the system operates with 100% water.

ESEER = 0.03.EER

100%

+ 0.33.EER

75%

+ 0.41.EER

50%

+ 0.23.EER

25%

Where 0.03, 0.33, 0.41 and 0.23 are specified weighting factors for use on calculating
ESEER.

Temperature

35°C

30°C

25°C

20°C

Capacity Requirement

100%

75%

50%

25%

Percentage of Total Hours

0.03

0.33

0.41

0.23