Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Cooling Performance AC Fans Extra Quiet

Ambient (°C)

25

30

35

40

Model

Vorlauftemperatur

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCC022DX-06AKK0

5

231.8

57.0

219.7

62.5

207.0

68.6

193.6

75.4

6

239.1

57.3

226.7

62.8

213.7

68.9

199.9

75.7

7

246.5

57.6

233.8

63.1

220.4

69.2

206.3

76.0

8

254.0

57.9

241.0

63.4

227.3

69.5

212.8

76.3

9

261.7

58.3

248.3

63.8

234.2

69.9

219.3

76.6

10

269.4

58.6

255.7

64.1

241.3

70.2

226.0

77.0

DCC024DX-06BKL0

5

259.8

67.2

246.2

73.4

231.6

80.2

216.1

87.7

6

267.9

67.6

253.9

73.8

238.9

80.6

222.9

88.1

7

276.0

68.0

261.6

74.1

246.3

81.0

229.9

88.5

8

284.3

68.4

269.5

74.5

253.8

81.4

236.9

88.9

9

292.8

68.8

277.6

74.9

261.4

81.8

244.1

89.3

10

301.3

69.2

285.7

75.4

269.1

82.2

251.4

89.7

DCC025DX-08BKL0

5

267.2

66.2

253.8

72.1

239.5

78.7

224.3

86.0

6

275.6

66.5

261.9

72.4

247.2

79.0

231.5

86.2

7

284.2

66.8

270.1

72.7

255.0

79.3

239.0

86.5

8

292.9

67.1

278.5

73.0

263.0

79.6

246.5

86.8

9

301.7

67.4

286.9

73.3

271.1

79.9

254.2

87.1

10

310.8

67.7

295.6

73.6

279.3

80.2

261.9

87.5

DCC027DX-06BLL0

5

285.2

77.3

270.3

84.2

254.1

91.7

236.7

99.9

6

294.0

77.8

278.6

84.6

262.0

92.2

244.1

100.4

7

302.9

78.2

287.1

85.1

270.0

92.6

251.6

100.9

8

311.9

78.6

295.6

85.5

278.1

93.1

259.2

101.4

9

321.0

79.1

304.3

86.0

286.3

93.6

266.9

101.9

10

330.3

79.6

313.2

86.5

294.7

94.1

274.8

102.4

DCC028DX-08BLL0

5

293.9

75.6

279.5

82.2

263.8

89.4

246.8

97.4

6

303.2

75.9

288.3

82.5

272.2

89.8

254.7

97.7

7

312.5

76.3

297.3

82.9

280.7

90.1

262.7

98.1

8

322.0

76.6

306.4

83.2

289.3

90.5

270.9

98.5

9

331.7

76.9

315.6

83.5

298.2

90.8

279.3

98.8

10

341.6

77.3

325.1

83.9

307.1

91.2

287.7

99.2

DCC030DX-06BLM0

5

308.5

84.8

291.8

92.3

273.9

100.4

254.8

109.4

6

317.8

85.3

300.6

92.8

282.3

101.0

262.6

110.0

7

327.2

85.9

309.6

93.4

290.7

101.7

270.5

110.7

8

336.8

86.5

318.7

94.0

299.3

102.3

278.5

111.3

9

346.5

87.1

328.0

94.7

308.0

102.9

286.7

112.0

10

356.4

87.7

337.3

95.3

316.8

103.6

295.0

112.6

DCC031DX-08BLM0

5

319.1

82.3

303.0

89.5

285.5

97.3

266.8

106.0

6

329.0

82.7

312.4

89.9

294.5

97.8

275.3

106.4

7

339.1

83.1

322.0

90.4

303.6

98.3

283.8

106.9

8

349.3

83.6

331.8

90.8

312.9

98.7

292.6

107.4

9

359.7

84.0

341.7

91.3

322.3

99.2

301.4

107.9

10

370.2

84.5

351.7

91.8

331.8

99.7

310.4

108.4

DCC032DX-06BMM0

5

328.4

92.1

310.3

100.2

291.1

109.0

270.6

118.8

6

338.1

92.8

319.6

100.9

299.8

109.8

278.7

119.5

7

348.1

93.5

329.0

101.6

308.6

110.5

286.9

120.3

8

358.1

94.2

338.5

102.4

317.6

111.3

295.3

121.0

9

368.3

94.9

348.1

103.1

326.6

112.0

303.8

121.8

10

378.6

95.6

357.9

103.9

335.8

112.8

312.4

122.6

DCC033DX-08BMM0

5

340.7

88.8

323.2

96.6

304.4

105.1

284.3

114.5

6

351.1

89.3

333.1

97.2

313.8

105.7

293.2

115.0

7

361.7

89.9

343.2

97.8

323.4

106.3

302.1

115.6

8

372.5

90.4

353.5

98.3

333.1

106.9

311.3

116.2

9

383.5

91.0

363.9

98.9

343.0

107.5

320.6

116.9

10

394.6

91.5

374.5

99.5

353.0

108.1

330.0

117.5



1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.