Chillers

DELTACHILL

Chillers

51

Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Regular Quiet Continued

ELECTRICAL DATA

DCC021SR-04BS00

DCC023SR-04BT00

DCC024SR-06BT00

Unit Data

Nominal Run Amps

(1)

A

146.4

159.7

168.3

Maximum Start Amps

(2)

A

363.3

432.2

440.8

Recommended Mains Fuse Size

A

160

200

200

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

6

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

4

4

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

43.1

47.5

47.5

Quantity

3

3

3

Motor Rating

kW

24.0

28.2

28.2

Sump Heater Rating

W

75

130

130

Start Amps (2)

A

260

320

320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

36.5

42.8

42.8

Circuit 2 Comp RLA (PFC)

N/A

N/A

N/A

Nominal Run Amps

A

126.7

145.6

154.2

Maximum Start Amps

A

350.2

422.8

431.4

Compressor Nominal Run Amps

A

36.5

42.8

42.8

Recommended Mains Fuse Size

A

160

200

200

Electronic Soft-start

Nominal Run Amps

A

146.4

159.7

168.3

Maximum Start Amps

A

259.3

304.2

312.8

Recommended Mains Fuse

A

160

200

200

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

126.7

145.6

154.2

Maximum Start Amps

A

246.2

294.8

303.4

Compressor Nominal Run Amps

A

36.5

42.8

42.8

Recommended Mains Fuse Size

A

160

200

200

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

6.2

6.2

Unit Nominal Run Amps

A

151.4

165.9

174.5

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

2.2

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.6

8.9

8.9

Unit Nominal Run Amps

A

153.0

168.6

177.2

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

3

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

6.3

8.0

Unit Nominal Run Amps

A

150.8

166.0

176.3

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

2.2

3

4

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

8

8

Unit Nominal Run Amps

A

152.7

167.7

176.3

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

3

4

4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.