Mechanical cooling ec fan high air flow, Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 87

Advertising
background image

Chillers

DELTACHILL

Chillers

87

Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Mechanical Cooling EC Fan high air flow

Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF014SR-04AL00

6

149.4

38.3

142.1

41.8

134.1

45.8

125.5

50.2

7

154.1

38.5

146.6

42.1

138.4

46.1

129.6

50.4

8

158.9

38.8

151.1

42.4

142.7

46.3

133.7

50.7

10

168.6

39.3

160.5

42.9

151.7

46.8

142.2

51.3

12

178.7

39.8

170.1

43.4

160.9

47.4

150.9

51.8

14

189.0

40.3

180.0

43.9

170.4

48.0

160.0

52.4

DCF017SR-04AM00

6

174.4

46.0

165.5

50.2

156.1

54.8

146.1

60.0

7

179.7

46.4

170.6

50.6

161.0

55.2

150.7

60.4

8

185.2

46.7

175.9

51.0

165.9

55.6

155.4

60.8

10

196.5

47.5

186.6

51.7

176.1

56.4

165.1

61.6

12

208.0

48.2

197.6

52.5

186.7

57.2

175.1

62.5

14

219.9

49.0

209.1

53.4

197.3

58.0

185.4

63.3

DCF021SR-04BS00

6

213.8

62.1

203.0

67.8

191.6

74.1

179.4

81.1

7

220.2

62.6

209.3

68.3

197.6

74.6

184.9

81.5

8

226.9

63.0

215.7

68.8

203.7

75.1

190.4

81.9

10

240.7

64.0

228.9

69.8

216.3

76.1

201.7

82.7

12

254.8

65.0

242.5

70.8

229.3

77.1

213.4

83.6

14

269.4

66.0

256.5

71.8

242.1

78.0

225.4

84.5

DCF025SR-06BT00

6

256.9

69.8

243.7

76.2

229.6

83.2

214.7

91.1

7

264.8

70.3

251.2

76.7

236.8

83.8

221.4

91.7

8

272.8

70.9

258.8

77.3

244.0

84.4

228.3

92.3

10

289.3

72.0

274.5

78.5

258.9

85.6

242.5

93.5

12

306.2

73.1

290.7

79.7

274.4

86.8

257.1

94.8

14

323.6

74.3

307.4

80.9

289.9

88.0

272.1

96.1


1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.

Advertising