Unit lifting, Deltachill ™ chillers, Installation data – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 128

Advertising
background image

DELTACHILL

Chillers

128

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Installation Data

Unit Lifting

Employ lifting specialists

Local codes and regulations relating to the lifting of this type of equipment should

be observed

Use the appropriate spreader bars/lifting slings (provided by others) with the eye

bolts/lugs provided

Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;

each individual chain must be capable of lifting the whole unit

Lifting eye bolt

Number of Condenser Fans

4 Fan

6 Fan

8 fan

10 fan

12 fan

Eyebolt size

M24

M30

M30

M30

M36

IMPORTANT

Do not use 1 chain between 2 lifting points to avoid load shift.

Only use lifting points provided.

Chains/slings MUST NOT interfere with the casing or fan assembly to
avoid damage.

Lift the unit slowly and evenly.

If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.

Lifting Dimensions










A

C

B

2300

A

B

C

4 Fan

mm

4000

1850

208

6 Fan

mm

4000

2186

210

8 Fan

mm

4000

3502

518

10 Fan

mm

4000

3336

1166

12 Fan

mm

5000

4745

1030

Advertising