Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 70

Advertising
background image

DELTACHILL

Chillers

70

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC042DX-12BSS0

DCC043DX-08BST0

DCC045DX-12BST0

Unit Data

Nominal Run Amps

(1)

A

288.4

291.7

301.7

Maximum Start Amps

(2)

A

505.3

564.2

574.2

Recommended Mains Fuse Size

A

315

315

355

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

12

8

12

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

12

8

12

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

43.1 / 43.1

47.5 / 43.1

47.5 / 43.1

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

24.0 / 24.0

28.2 / 24.0

28.2 / 24.0

Sump Heater Rating

W

75

130 + 75

130 + 75

Start Amps (2)

A

260 / 260

320 / 260

320 / 260

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

36.5

42.8

42.8

Circuit 2 Comp RLA (PFC)

36.5

36.5

36.5

Nominal Run Amps

A

248.9

257.8

267.8

Maximum Start Amps

A

472.4

535.0

545.0

Compressor Nominal Run Amps

A

36.5 / 36.5

42.8 / 36.5

42.8 / 36.5

Recommended Mains Fuse Size

A

315

315

355

Electronic Soft-start

Nominal Run Amps

A

288.4

291.7

301.7

Maximum Start Amps

A

401.3

388.67

398.67

Recommended Mains Fuse

A

315

315

355

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

248.9

257.8

267.8

Maximum Start Amps

A

368.4

364.2

374.2

Compressor Nominal Run Amps

A

36.5 / 36.5

42.8 / 36.5

42.8 / 36.5

Recommended Mains Fuse Size

A

315

315

355

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

12

12

12

Unit Nominal Run Amps

A

300.4

303.7

313.7

Recommended Mains Fuse Size

A

315

355

355

Motor Rating

kW

5.5

5.5

5.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

14

14

14

Unit Nominal Run Amps

A

302.4

305.7

315.7

Recommended Mains Fuse Size

A

315

355

355

Motor Rating

kW

7.5

7.5

7.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

299.6

302.9

312.9

Recommended Mains Fuse Size

A

315

355

355

Motor Rating

kW

5.5

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

14.8

14.8

Unit Nominal Run Amps

A

299.6

306.5

316.5

Recommended Mains Fuse Size

A

315

355

355

Motor Rating

kW

5.5

7.5

7.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.