Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Free Cool Chiller Regular Quiet Continued

ELECTRICAL DATA

DCF020DR-06BFK0

DCF023DR-06BKK0

DCF026DR-06BKL0

Unit Data

Nominal Run Amps

(1)

A

140.5

159.1

179.2

Maximum Start Amps

A

413.0

341.1

396.1

Recommended Mains Fuse Size

A

160

200

200

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

6

6

6

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

6

6

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 33.0

33.0 / 33.0

33.0 / 43.1

Quantity

1 + 2

2 + 2

2 + 2

Motor Rating

kW

28.2 / 18.8

18.8 / 18.8

18.8 / 24.0

Sump Heater Rating

W

130 / 75

75

75

Start Amps

A

320 / 215

215 / 215

215 / 260

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

28.5

28.5

Circuit 2 Comp RLA (PFC)

28.5

28.5

36.5

Nominal Run Amps

A

126.8

141.0

157.0

Maximum Start Amps

A

404.0

327.5

380.5

Compressor Nominal Run Amps

A

42.8 / 28.5

28.5 / 28.5

28.5 / 36.5

Recommended Mains Fuse Size

A

160

200

200

Electronic Soft-start

Nominal Run Amps

A

140.5

159.1

179.2

Maximum Start Amps

A

285.0

255.1

292.1

Recommended Mains Fuse

A

160.0

200.0

200.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

126.8

141.0

157.0

Maximum Start Amps

A

276.0

241.5

276.5

Compressor Nominal Run Amps

A

42.8 / 28.5

28.5 / 28.5

28.5 / 36.5

Recommended Mains Fuse Size

A

160

200

200

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

6

6

6

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

12

Unit Nominal Run Amps

A

149.4

168.0

191.2

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

4

4

5.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.8

11.8

11.8

Unit Nominal Run Amps

A

152.3

170.9

191.0

Recommended Mains Fuse Size

A

200

200

250

Motor Rating

kW

5.5

5.5

5.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8

8

11.2

Unit Nominal Run Amps

A

148.5

167.1

190.4

Recommended Mains Fuse Size

A

160

200

200

Motor Rating

kW

4

4

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

14.8

Unit Nominal Run Amps

A

151.7

170.3

194.0

Recommended Mains Fuse Size

A

160

200

200

Motor Rating

kW

5.5

5.5

7.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.