Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Free Cool Chiller Regular Quiet Continued

ELECTRICAL DATA

DCF039DR-10BMS0

DCF044DR-10BSS0

DCF014SX-04AL00

Unit Data

Nominal Run Amps

(1)

A

269.2

303.4

96.1

Maximum Start Amps

A

541.7

520.3

313.1

Recommended Mains Fuse Size

A

315

315

125

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

10

10

4

Full Load Amps

A

4.3

4.3

2.5

Locked Rotor Amps

A

15

15

8.8

Motor Rating

kW

2

2

1.27

Condenser Fan - Per Fan (EC)

Quantity

10

10

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 43.1

43.1 / 43.1

43.1

Quantity

2 + 3

3 + 3

2

Motor Rating

kW

28.2 / 24.0

24.0 / 24.0

24.0

Sump Heater Rating

W

130 + 75

75

75

Start Amps

A

320 / 260

260 / 260

260

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

36.5

36.5

Circuit 2 Comp RLA (PFC)

36.5

36.5

N/A

Nominal Run Amps

A

240.0

263.9

83.0

Maximum Start Amps

A

517.2

487.4

306.5

Compressor Nominal Run Amps

A

42.8 / 36.5

36.5 / 36.5

36.5

Recommended Mains Fuse Size

A

315

315

125

Electronic Soft-start

Nominal Run Amps

A

269.2

303.4

96.1

Maximum Start Amps

A

413.7

416.3

209.1

Recommended Mains Fuse

A

315.0

315.0

125.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

240.0

263.9

83.0

Maximum Start Amps

A

389.2

383.4

202.5

Compressor Nominal Run Amps

A

42.8 / 36.5

36.5 / 36.5

36.5

Recommended Mains Fuse Size

A

315

315

125

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

10

10

N/A

Full Load Amps

A

4.5

4.5

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

N/A

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

14

14

6.6

Unit Nominal Run Amps

A

283.2

317.4

102.7

Recommended Mains Fuse Size

A

315

355

125

Motor Rating

kW

7.5

7.5

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

20.8

20.8

9.8

Unit Nominal Run Amps

A

290.0

324.2

105.9

Recommended Mains Fuse Size

A

315

355

125

Motor Rating

kW

11

11

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

14.8

14.8

6.3

Unit Nominal Run Amps

A

284.0

318.2

102.4

Recommended Mains Fuse Size

A

315

355

125

Motor Rating

kW

7.5

7.5

3

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

21.2

21.2

8

Unit Nominal Run Amps

A

290.4

324.6

104.1

Recommended Mains Fuse Size

A

315

355

125

Motor Rating

kW

11

11

4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.