Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 89

Advertising
background image

Chillers

DELTACHILL

Chillers

89

Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF026DR-06BKL0

6

264.4

69.6

250.9

76.3

236.6

83.7

221.5

92.0

7

272.5

70.2

258.7

76.8

244.1

84.2

228.6

92.6

8

280.8

70.7

266.7

77.3

251.7

84.8

235.9

93.1

10

297.8

71.7

282.9

78.4

267.3

85.9

250.7

94.2

12

315.1

72.8

299.8

79.5

283.5

87.0

266.2

95.4

14

333.4

74.0

317.2

80.7

300.2

88.2

282.1

96.6

DCF029DR-06BLL0

6

291.4

80.9

276.7

88.2

261.0

96.4

244.3

105.6

7

300.4

81.4

285.3

88.8

269.2

97.1

252.1

106.2

8

309.5

82.0

294.1

89.4

277.6

97.7

260.0

106.9

10

328.2

83.2

311.7

90.6

294.6

98.9

276.4

108.2

12

347.0

84.3

330.3

91.9

312.4

100.3

293.4

109.6

14

367.4

85.7

349.5

93.2

330.8

101.6

310.9

110.9

DCF032DR-08BLM0

6

323.9

84.3

307.6

92.0

290.2

100.6

271.6

110.1

7

333.9

84.9

317.2

92.6

299.3

101.2

280.3

110.8

8

344.1

85.5

327.0

93.3

308.6

101.9

289.1

111.5

10

364.9

86.7

346.9

94.6

327.7

103.2

307.1

112.9

12

386.4

88.0

367.5

95.9

347.4

104.6

325.8

114.3

14

408.6

89.3

388.7

97.2

367.6

106.0

345.0

115.7

DCF035DR-08BMM0

6

346.4

91.8

328.8

100.2

310.2

109.5

290.4

119.8

7

357.1

92.6

339.0

101.0

319.9

110.2

299.6

120.6

8

367.9

93.3

349.3

101.7

329.7

111.0

308.9

121.4

10

390.0

94.8

370.5

103.3

349.8

112.6

328.0

123.0

12

412.8

96.3

392.3

104.9

370.7

114.3

347.8

124.7

14

436.4

97.8

414.9

106.5

392.2

116.0

368.0

126.4

DCF039DR-10BMS0

6

399.1

103.8

379.0

113.3

357.5

123.9

334.5

135.7

7

411.5

104.5

390.8

114.1

368.8

124.7

345.2

136.5

8

424.1

105.2

402.9

114.9

380.3

125.5

356.1

137.3

10

449.9

106.7

427.6

116.4

403.8

127.1

378.4

139.0

12

476.5

108.3

453.1

118.0

427.8

128.7

401.4

140.6

14

503.8

109.8

479.3

119.6

453.0

130.4

425.4

142.4

DCF044DR-10BSS0

6

440.0

119.0

417.9

129.9

394.2

142.1

368.8

155.6

7

453.7

119.8

430.9

130.8

406.7

142.9

380.6

156.5

8

467.5

120.6

444.2

131.6

419.3

143.8

392.6

157.4

10

495.9

122.3

471.4

133.4

445.3

145.6

417.3

159.3

12

525.2

124.0

499.6

135.1

471.5

147.3

442.7

161.1

14

555.3

125.8

528.5

137.0

499.4

149.2

469.3

163.1

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.