Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Code

Description

Auto Reset

(Yes/No)

Unit Disabled

(Yes/No)

Component

Disabled
(Yes/No)

Cause

Action

AL030

EEPROM Fault EVD1

No

Yes

There has been

mismatch with between

data in the EVD and

the controller

Reset the alarm / Replace

EVD if necessary

AL031

EEV Motor Fault EVD1

No

Yes

The stepper motor has

malfunctioned

Check: Motor / Wiring

AL032

MOP Alarm EVD1

No

Yes

The Evaporating
temperature has

exceeded the MOP

limit

The valve will close to

reduce operating pressure

AL033

LOP Alarm EVD1

No

Yes

The Evaporating
temperature has

exceeded the LOP limit

The Valve will open to

increase operating pressure

AL034

Low Superheat EVD1

No

Yes

The superheat in circuit

1 is low

Check: EEV Settings

AL035

S2 Probe Fault EVD1

No

Yes

The Evaporator

Temperature probe is

out of range

Check: Temperature probe /

Wiring

AL036

High Superheat EVD1

No

Yes

The superheat in circuit

1 is high

Check: EEV Settings

AL037

S1 Probe Fault EVD2

No

Yes

The Evaporator

pressure probe is out of

range

Check: Pressure probe /

Wiring

AL038

EEPROM Fault EVD2

No

Yes

There has been

mismatch with between

data in the EVD and

the controller

Reset the alarm / Replace

EVD if necessary

AL039

EEV Motor Fault EVD2

No

Yes

The stepper motor has

malfunctioned

Check: Motor / Wiring

AL040

MOP Alarm EVD2

No

Yes

The Evaporating
temperature has

exceeded the MOP

limit

The valve will close to

reduce operating pressure

AL041

LOP Alarm EVD2

No

Yes

The Evaporating
temperature has

exceeded the LOP limit

The Valve will open to

increase operating pressure

AL042

Low Superheat EVD2

No

Yes

The superheat in circuit

2 is low

Check: EEV Settings

AL043

S2 Probe Fault EVD2

No

Yes

The Evaporator

Temperature probe is

out of range

Check: Temperature probe /

Wiring

AL044

High Superheat EVD2

No

Yes

The superheat in circuit

2 is high

Check: EEV Settings

AL045

Leak Detector 1 Fault

Yes

No

Yes

The output from the

leak detector is out of

range

Check: Leak detector /

Wiring

AL046

Leak Detector 2 Fault

AL047

Possible Leak Circ.1

Yes

No

No

The reading from the

leak detector is above

the threshold

Check: Pipe work around

the leak detector

AL048

Possible Leak Circ.2

AL049

Cct1 Hours Limit Comp1

Yes

No

No

The hours run for the

compressor has

exceeded the threshold

If component is functioning

correctly perform

maintenance and reset

hours

AL050

Cct1 Hours Limit Comp2

AL051

Cct1 Hours Limit Comp3

AL052

Cct2 Hours Limit Comp1

AL053

Cct2 Hours Limit Comp2

AL054

Cct2 Hours Limit Comp3