Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 164
![background image](/manuals/370932/164/background.png)
DELTACHILL
™
Chillers
164
Chillers
Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013
Code
Description
Auto Reset
(Yes/No)
Unit Disabled
(Yes/No)
Component
Disabled
(Yes/No)
Cause
Action
AL030
EEPROM Fault EVD1
No
Yes
There has been
mismatch with between
data in the EVD and
the controller
Reset the alarm / Replace
EVD if necessary
AL031
EEV Motor Fault EVD1
No
Yes
The stepper motor has
malfunctioned
Check: Motor / Wiring
AL032
MOP Alarm EVD1
No
Yes
The Evaporating
temperature has
exceeded the MOP
limit
The valve will close to
reduce operating pressure
AL033
LOP Alarm EVD1
No
Yes
The Evaporating
temperature has
exceeded the LOP limit
The Valve will open to
increase operating pressure
AL034
Low Superheat EVD1
No
Yes
The superheat in circuit
1 is low
Check: EEV Settings
AL035
S2 Probe Fault EVD1
No
Yes
The Evaporator
Temperature probe is
out of range
Check: Temperature probe /
Wiring
AL036
High Superheat EVD1
No
Yes
The superheat in circuit
1 is high
Check: EEV Settings
AL037
S1 Probe Fault EVD2
No
Yes
The Evaporator
pressure probe is out of
range
Check: Pressure probe /
Wiring
AL038
EEPROM Fault EVD2
No
Yes
There has been
mismatch with between
data in the EVD and
the controller
Reset the alarm / Replace
EVD if necessary
AL039
EEV Motor Fault EVD2
No
Yes
The stepper motor has
malfunctioned
Check: Motor / Wiring
AL040
MOP Alarm EVD2
No
Yes
The Evaporating
temperature has
exceeded the MOP
limit
The valve will close to
reduce operating pressure
AL041
LOP Alarm EVD2
No
Yes
The Evaporating
temperature has
exceeded the LOP limit
The Valve will open to
increase operating pressure
AL042
Low Superheat EVD2
No
Yes
The superheat in circuit
2 is low
Check: EEV Settings
AL043
S2 Probe Fault EVD2
No
Yes
The Evaporator
Temperature probe is
out of range
Check: Temperature probe /
Wiring
AL044
High Superheat EVD2
No
Yes
The superheat in circuit
2 is high
Check: EEV Settings
AL045
Leak Detector 1 Fault
Yes
No
Yes
The output from the
leak detector is out of
range
Check: Leak detector /
Wiring
AL046
Leak Detector 2 Fault
AL047
Possible Leak Circ.1
Yes
No
No
The reading from the
leak detector is above
the threshold
Check: Pipe work around
the leak detector
AL048
Possible Leak Circ.2
AL049
Cct1 Hours Limit Comp1
Yes
No
No
The hours run for the
compressor has
exceeded the threshold
If component is functioning
correctly perform
maintenance and reset
hours
AL050
Cct1 Hours Limit Comp2
AL051
Cct1 Hours Limit Comp3
AL052
Cct2 Hours Limit Comp1
AL053
Cct2 Hours Limit Comp2
AL054
Cct2 Hours Limit Comp3