Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 21
Chillers
DELTACHILL
™
Chillers
21
Installation, Commissioning and Maintenance Manual :7025232 12/ 2013
Cooling Performance EC Fans
Ambient (°C)
25
30
35
40
Model
Vorlauftemperatur
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC011DR-04ACC0
5
117.1
26.7
111.5
29.4
105.5
32.5
99.2
35.9
6
120.8
26.8
115.1
29.6
108.9
32.6
102.5
36.0
7
124.8
27.0
118.8
29.7
112.5
32.8
105.8
36.1
8
128.5
27.1
122.5
29.9
116.1
32.9
109.3
36.3
9
132.5
27.3
126.3
30.0
119.7
33.0
112.7
36.4
10
136.6
27.5
130.2
30.2
123.4
33.2
116.3
36.6
DCC013DR-04ACD0
5
133.2
31.6
126.9
34.7
120.1
38.1
112.8
41.8
6
137.5
31.8
131.0
34.8
124.0
38.2
116.5
42.0
7
141.8
31.9
135.1
35.0
128.0
38.4
120.3
42.1
8
146.2
32.1
139.4
35.2
132.1
38.6
124.2
42.3
9
150.8
32.3
143.7
35.4
136.2
38.7
128.2
42.5
10
155.3
32.5
148.1
35.5
140.4
38.9
132.2
42.6
DCC014DR-04ADD0
5
147.1
36.5
140.3
39.9
132.8
43.6
124.8
47.6
6
151.8
36.7
144.8
40.0
137.2
43.8
128.9
47.8
7
156.6
36.9
149.4
40.2
141.6
44.0
133.1
48.0
8
161.5
37.0
154.1
40.4
146.0
44.1
137.3
48.2
9
166.4
37.2
158.9
40.6
150.6
44.3
141.7
48.4
10
171.5
37.4
163.7
40.8
155.2
44.5
146.1
48.6
DCC015DR-04ADF0
5
160.3
40.1
152.6
43.8
144.3
47.9
135.4
52.3
6
165.4
40.4
157.5
44.1
149.0
48.1
139.8
52.5
7
170.6
40.6
162.4
44.3
153.7
48.3
144.3
52.8
8
175.9
40.8
167.5
44.6
158.5
48.6
148.9
53.0
9
181.2
41.1
172.7
44.8
163.5
48.9
153.6
53.3
10
186.7
41.3
177.9
45.1
168.4
49.1
158.3
53.6
DCC016DR-04AJJ0
5
166.6
42.0
158.3
46.0
149.5
50.4
140.3
55.3
6
172.0
42.2
163.5
46.3
154.5
50.7
145.0
55.6
7
177.5
42.5
168.8
46.5
159.6
50.9
149.9
55.8
8
183.1
42.7
174.2
46.7
164.8
51.2
154.7
56.0
9
188.8
42.9
179.7
47.0
170.0
51.4
159.8
56.3
10
194.6
43.2
185.3
47.2
175.4
51.7
164.8
56.6
DCC018DR-04BJK0
5
193.9
50.4
184.2
55.4
173.9
60.9
163.1
67.0
6
200.1
50.7
190.1
55.7
179.6
61.2
168.4
67.3
7
206.3
51.1
196.1
56.0
185.3
61.5
173.9
67.6
8
212.7
51.4
202.2
56.4
191.1
61.9
179.4
67.9
9
219.1
51.7
208.4
56.7
197.1
62.2
185.1
68.3
10
225.7
52.1
214.7
57.1
203.1
62.5
190.8
68.6
DCC019DR-04AFK0
5
200.4
51.5
190.3
56.5
179.6
61.9
168.2
67.9
6
206.7
51.9
196.4
56.8
185.4
62.3
173.7
68.3
7
213.2
52.2
202.5
57.2
191.2
62.6
179.3
68.7
8
219.7
52.6
208.8
57.6
197.2
63.0
184.9
69.0
9
226.3
53.0
215.2
58.0
203.3
63.4
190.7
69.4
10
233.1
53.4
221.6
58.3
209.5
63.8
196.5
69.8
DCC020DR-06AFK0
5
205.6
48.6
195.5
53.4
184.8
58.7
173.5
64.5
6
212.2
48.9
201.8
53.7
190.8
59.0
179.2
64.8
7
218.9
49.2
208.2
54.0
197.0
59.3
185.1
65.1
8
225.7
49.5
214.8
54.3
203.3
59.6
191.0
65.4
9
232.6
49.8
221.5
54.6
209.6
59.9
197.1
65.7
10
239.7
50.1
228.2
54.9
216.1
60.2
203.2
66.0
DCC021DR-04AKK0
5
225.3
59.1
213.8
65.0
201.7
71.6
188.9
78.8
6
232.3
59.5
220.6
65.4
208.2
72.0
195.1
79.2
7
239.5
60.0
227.5
65.9
214.8
72.4
201.3
79.7
8
246.8
60.4
234.5
66.3
221.5
72.8
207.7
80.1
9
254.3
60.9
241.6
66.8
228.3
73.3
214.1
80.5
10
261.8
61.3
248.9
67.2
235.2
73.7
220.7
81.0
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.