Electrical data free cool chiller regular quiet, Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 102
DELTACHILL
™
Chillers
102
Chillers
Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013
Electrical Data Free Cool Chiller Regular Quiet
ELECTRICAL DATA
DCF014SR-04AL00
DCF017SR-04AM00
DCF021SR-04BS00
Unit Data
Nominal Run Amps
(1)
A
104.1
113.0
147.2
Maximum Start Amps
A
321.1
385.5
364.1
Recommended Mains Fuse Size
A
125
125
160
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
4
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
4
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1
47.5
43.1
Quantity
2
2
3
Motor Rating
kW
24.0
28.2
24.0
Sump Heater Rating
W
75
130
75
Start Amps
A
260
320
260
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
42.8
36.5
Circuit 2 Comp RLA (PFC)
N/A
N/A
N/A
Nominal Run Amps
A
91.0
103.6
127.5
Maximum Start Amps
A
314.5
380.8
351.0
Compressor Nominal Run Amps
A
36.5
42.8
36.5
Recommended Mains Fuse Size
A
125
125
160
Electronic Soft-start
Nominal Run Amps
A
104.1
113.0
147.2
Maximum Start Amps
A
217.1
257.5
260.1
Recommended Mains Fuse
A
125.0
125.0
160.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
91.0
103.6
127.5
Maximum Start Amps
A
210.5
252.8
247.0
Compressor Nominal Run Amps
A
36.5
42.8
36.5
Recommended Mains Fuse Size
A
125
125
160
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
4
4
4
Full Load Amps
A
4.5
4.5
4.5
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.86
2.86
2.86
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.6
8.9
8.9
Unit Nominal Run Amps
A
110.7
121.9
156.1
Recommended Mains Fuse Size
A
125
160
200
Motor Rating
kW
3
4
4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
9.8
11.8
11.8
Unit Nominal Run Amps
A
113.9
124.8
159.0
Recommended Mains Fuse Size
A
125
160
200
Motor Rating
kW
4
5.5
5.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
8
Unit Nominal Run Amps
A
110.4
119.3
155.2
Recommended Mains Fuse Size
A
125
160
200
Motor Rating
kW
3
3
4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
8
8
11.2
Unit Nominal Run Amps
A
112.1
121.0
158.4
Recommended Mains Fuse Size
A
125
160
200
Motor Rating
kW
4
4
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.