Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 64

Advertising
background image

DELTACHILL

Chillers

64

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC015DX-04ADF0

DCC016DX-04AJJ0

DCC018DX-04BJK0

Unit Data

Nominal Run Amps

(1)

A

100.6

118.0

135.0

Maximum Start Amps

(2)

A

373.1

271.0

317.0

Recommended Mains Fuse Size

A

125

160

160

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

6

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

4

4

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 43.1

27.0 / 27.0

33.0 / 27.0

Quantity

1 + 1

2 + 2

2 + 2

Motor Rating

kW

28.2 / 24.0

13.7 / 13.7

18.8 / 13.7

Sump Heater Rating

W

130 + 75

75

75

Start Amps (2)

A

320 / 260

180 / 180

215 / 180

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

20.9

28.5

Circuit 2 Comp RLA (PFC)

36.5

20.9

20.9

Nominal Run Amps

A

89.3

93.4

113.7

Maximum Start Amps

A

366.5

252.6

300.2

Compressor Nominal Run Amps

A

42.8 / 36.5

20.9 / 20.9

28.5 / 20.9

Recommended Mains Fuse Size

A

125

160

160

Electronic Soft-start

Nominal Run Amps

A

100.55

118

135.04

Maximum Start Amps

A

245.06

199

231.02

Recommended Mains Fuse

A

125

160

160

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

89.3

93.4

113.7

Maximum Start Amps

A

238.5

180.6

214.2

Compressor Nominal Run Amps

A

42.8 / 36.5

20.9 / 20.9

28.5 / 20.9

Recommended Mains Fuse Size

A

125

160

160

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

5

Unit Nominal Run Amps

A

105.6

123.0

140.0

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

6.6

6.6

Unit Nominal Run Amps

A

105.6

124.6

141.6

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

2.2

3

3

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

4.5

4.5

Unit Nominal Run Amps

A

105.0

122.5

139.5

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

6.3

Unit Nominal Run Amps

A

106.9

124.3

141.3

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

3

3

3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.