Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 66
DELTACHILL
™
Chillers
66
Chillers
Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013
Electrical Data Extra Quiet Continued
ELECTRICAL DATA
DCC022DX-06AKK0
DCC024DX-06BKL0
DCC025DX-08BKL0
Unit Data
Nominal Run Amps
(1)
A
147.1
167.2
172.2
Maximum Start Amps
(2)
A
329.1
384.1
389.1
Recommended Mains Fuse Size
A
200
200
200
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
6
6
8
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
6
6
8
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
33.0 / 33.0
43.1 / 33.0
43.1 / 33.0
Quantity
2 + 2
2 + 2
2 + 2
Motor Rating
kW
18.8 / 18.8
24.0 / 18.8
24.0 / 18.8
Sump Heater Rating
W
75
75
75
Start Amps (2)
A
215 / 215
260 / 215
260 / 215
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
28.5
36.5
36.5
Circuit 2 Comp RLA (PFC)
28.5
28.5
28.5
Nominal Run Amps
A
129.0
145.0
150.0
Maximum Start Amps
A
315.5
368.5
373.5
Compressor Nominal Run Amps
A
28.5 / 28.5
36.5 / 28.5
36.5 / 28.5
Recommended Mains Fuse Size
A
200
200
200
Electronic Soft-start
Nominal Run Amps
A
147.1
167.2
172.2
Maximum Start Amps
A
243.1
280.1
285.1
Recommended Mains Fuse
A
200
200
200
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
129.0
145.0
150.0
Maximum Start Amps
A
229.5
264.5
269.5
Compressor Nominal Run Amps
A
28.5 / 28.5
36.5 / 28.5
36.5 / 28.5
Recommended Mains Fuse Size
A
200
200
200
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.2
6.2
6.2
Unit Nominal Run Amps
A
153.3
173.4
178.4
Recommended Mains Fuse Size
A
200
200
250
Motor Rating
kW
3
3
3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
156.0
176.1
181.1
Recommended Mains Fuse Size
A
200
200
250
Motor Rating
kW
4
4
4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
8.0
8.0
Unit Nominal Run Amps
A
153.4
175.2
180.2
Recommended Mains Fuse Size
A
200
200
250
Motor Rating
kW
3
4
4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
8
11.2
11.2
Unit Nominal Run Amps
A
155.1
178.4
183.4
Recommended Mains Fuse Size
A
200
200
250
Motor Rating
kW
4
5.5
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.