Temperature control, Chillers deltachill – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 9

Advertising
background image

Chillers

DELTACHILL

Chillers

9

Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Temperature Control

Airedale recognises that all chiller applications are different but fall mainly into 2
application categories; Variable Supply Temperature and Constant Supply Temperature.

The onboard microprocessor has the capability of satisfying either control requirement as
illustrated below.

Using the Airedale Variable Supply Temperature control scheme,

energy savings are available when compared with previous schemes and that of the
Constant Supply Temperature application.

Variable Supply Temperature control schemes offer energy savings where the supply
water temperature is not critical to its operation.

Selection of the best application control scheme can be made via a soft switch in the
microprocessor during initial commissioning.

The microprocessor maintains the set supply Chilled Water temperature by sensing the
return and supply water temperatures and ambient air temperature and adjusting the
compressor loading as required.

Examples based on Model DCC033DR-08BMH0 having 6 Stages of Cooling

Key:

1

Return Water Temperature

2

Mean Value

3

Supply Water Temperature

4

Compressor Off

Variable Supply
Temperature Control

Wa

te

r Te

m

pe

ratu

re

°C

6

7

8

9

10

11

12

13

14

1

3

4

2

20% / 1

40% / 2

50% / 3

60% / 4

80% / 5

100% / 6

Chiller Capacity % / Cooling Stage Sequence

Constant Supply
Temperature Control

Wa

te

r Te

m

pe

ratu

re

°C

6

7

8

9

10

11

12

13

14

20% / 1

40% / 2

50% / 3

60% / 4

80% / 5

100% / 6

1

3

Chiller Capacity % / Cooling Stage Sequence

CAUTION

Factory set to Variable Supply Temperature Control unless otherwise stated
at order.

Only when the mode selection has been set can the unit be enabled.