Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF026DX-08BKL0

6

270.4

69.6

256.2

75.8

240.8

82.7

224.3

90.4

7

278.7

70.0

264.1

76.2

248.3

83.1

231.3

90.8

8

287.1

70.4

272.1

76.6

255.9

83.5

238.4

91.2

10

304.3

71.2

288.4

77.4

271.3

84.3

252.9

92.1

12

321.9

72.1

305.2

78.3

287.3

85.2

267.9

93.0

14

340.1

73.0

322.5

79.2

303.6

86.2

283.3

94.0

DCF029DX-08BLL0

6

296.9

79.7

281.3

86.6

264.2

94.3

245.6

102.8

7

305.9

80.2

289.8

87.1

272.2

94.8

253.1

103.3

8

315.1

80.6

298.5

87.6

280.4

95.2

260.8

103.8

10

333.7

81.5

316.2

88.5

297.2

96.3

276.4

104.8

12

352.9

82.5

334.5

89.5

314.3

97.3

292.5

105.9

14

372.6

83.5

353.1

90.6

332.0

98.4

309.1

107.1

DCF032DX-08BLM0

6

321.0

87.3

303.5

94.8

284.5

103.2

264.0

112.5

7

330.5

87.9

312.5

95.4

293.0

103.8

271.9

113.1

8

340.3

88.4

321.8

96.1

301.7

104.5

280.0

113.8

10

360.1

89.6

340.5

97.3

319.3

105.8

296.5

115.1

12

380.4

90.9

359.8

98.6

337.4

107.1

313.4

116.6

14

401.2

92.2

379.5

100.0

356.0

108.5

330.7

118.0

DCF035DX-08BMM0

6

341.7

94.7

322.7

102.9

302.2

111.9

280.1

122.0

7

351.7

95.4

332.2

103.6

311.1

112.7

288.4

122.8

8

361.9

96.1

341.8

104.4

320.1

113.5

296.8

123.6

10

382.7

97.6

361.4

105.9

338.5

115.1

313.9

125.3

12

404.0

99.1

381.5

107.5

357.3

116.8

331.4

127.0

14

425.7

100.6

402.0

109.2

376.6

118.5

349.4

128.8

DCF039DX-10BMS0

6

395.8

107.4

374.2

116.7

350.8

127.0

325.5

138.4

7

407.6

108.1

385.5

117.4

361.4

127.7

335.4

139.2

8

419.7

108.8

396.9

118.2

372.1

128.5

345.4

140.0

10

444.2

110.3

420.1

119.7

394.0

130.1

365.8

141.6

12

469.4

111.8

444.0

121.3

416.4

131.7

386.8

143.3

14

495.2

113.3

468.4

122.9

439.4

133.4

408.3

145.1

DCF044DX-12BSS0

6

444.6

119.8

421.1

130.2

395.4

141.7

367.4

154.5

7

458.1

120.5

433.9

130.9

407.5

142.4

378.7

155.2

8

471.8

121.2

446.9

131.6

419.8

143.2

390.2

156.0

10

499.8

122.5

473.5

133.0

444.8

144.7

413.7

157.6

12

528.6

124.0

500.8

134.5

470.6

146.3

437.8

159.2

14

558.1

125.5

528.8

136.1

497.0

147.9

462.6

160.9

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.

Advertising