Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Free Cool Chiller Extra Quiet Continued

ELECTRICAL DATA

DCF013DX-04ACD0

DCF014DX-04ADD0

DCF015DX-04ADF0

Unit Data

Nominal Run Amps

(1)

A

86.1

96.1

100.6

Maximum Start Amps

A

313.1

313.1

377.5

Recommended Mains Fuse Size

A

125

125

125

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

4

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

4

4

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0 / 43.1

43.1 / 43.1

43.1 / 47.5

Quantity

1 + 1

1 + 1

1 + 1

Motor Rating

kW

18.8 / 24.0

24.0 / 24.0

24.0 / 28.2

Sump Heater Rating

W

75

75

75

Start Amps

A

215 / 260

260 / 260

260 / 320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

36.5

36.5

Circuit 2 Comp RLA (PFC)

36.5

36.5

42.8

Nominal Run Amps

A

75.0

83.0

89.3

Maximum Start Amps

A

306.5

306.5

372.8

Compressor Nominal Run Amps

A

28.5 / 36.5

36.5 / 36.5

36.5 / 42.8

Recommended Mains Fuse Size

A

125

125

125

Electronic Soft-start

Nominal Run Amps

A

86.1

96.1

100.6

Maximum Start Amps

A

199.0

209.1

245.1

Recommended Mains Fuse

A

125.0

125.0

125.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

75.0

83.0

89.3

Maximum Start Amps

A

194.5

202.5

238.5

Compressor Nominal Run Amps

A

28.5 / 36.5

36.5 / 36.5

36.5 / 42.8

Recommended Mains Fuse Size

A

125

125

125

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

N/A

N/A

N/A

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.6

6.6

6.6

Unit Nominal Run Amps

A

92.7

102.7

107.2

Recommended Mains Fuse Size

A

125

125

125

Motor Rating

kW

3

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

9.8

9.8

9.8

Unit Nominal Run Amps

A

95.9

105.9

110.4

Recommended Mains Fuse Size

A

125

125

125

Motor Rating

kW

4

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

6.3

Unit Nominal Run Amps

A

92.4

102.4

106.9

Recommended Mains Fuse Size

A

125

125

125

Motor Rating

kW

3

3

3

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8

8

8

Unit Nominal Run Amps

A

94.1

104.1

108.6

Recommended Mains Fuse Size

A

125

125

125

Motor Rating

kW

4

4

4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.