Electrical data regular quiet, Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 50

Advertising
background image

DELTACHILL

Chillers

50

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Regular Quiet

ELECTRICAL DATA

DCC011SR-04AK00

DCC014SR-04AL00

DCC017SR-04AM00

Unit Data

Nominal Run Amps

(1)

A

83.2

103.3

112.2

Maximum Start Amps

(2)

A

265.2

320.3

384.7

Recommended Mains Fuse Size

A

100

125

125

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

4

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

4

4

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0

43.1

47.5

Quantity

2

2

2

Motor Rating

kW

18.8

24.0

28.2

Sump Heater Rating

W

75

75

130

Start Amps (2)

A

215

260

320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

36.5

42.8

Circuit 2 Comp RLA (PFC)

N/A

N/A

N/A

Nominal Run Amps

A

74.2

90.2

102.8

Maximum Start Amps

A

260.7

313.7

380.0

Compressor Nominal Run Amps

A

28.5

36.5

42.8

Recommended Mains Fuse Size

A

100

125

125

Electronic Soft-start

Nominal Run Amps

A

83.24

103.32

112.18

Maximum Start Amps

A

179.22

216.26

256.69

Recommended Mains Fuse

A

100

125

125

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

74.2

90.2

102.8

Maximum Start Amps

A

174.7

209.7

252.0

Compressor Nominal Run Amps

A

28.51

36.48

42.78

Recommended Mains Fuse Size

A

100

125

125

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

5

Unit Nominal Run Amps

A

88.2

108.3

117.2

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

6.6

Unit Nominal Run Amps

A

88.2

108.3

118.8

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

2.2

2.2

3

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

4.5

4.5

Unit Nominal Run Amps

A

87.7

107.8

116.6

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

6.3

Unit Nominal Run Amps

A

89.5

109.6

118.5

Recommended Mains Fuse Size

A

100

125

160

Motor Rating

kW

3

3

3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.