Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 67
Chillers
DELTACHILL
™
Chillers
67
Installation, Commissioning and Maintenance Manual :7025232 12/ 2013
Electrical Data Extra Quiet Continued
ELECTRICAL DATA
DCC027DX-06BLL0
DCC028DX-08BLL0
DCC030DX-06BLM0
Unit Data
Nominal Run Amps
(1)
A
187.2
192.2
196.1
Maximum Start Amps
(2)
A
404.2
409.2
468.6
Recommended Mains Fuse Size
A
250
250
250
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
6
8
6
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
6
8
6
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1 / 43.1
43.1 / 43.1
47.5 / 43.1
Quantity
2 + 2
2 + 2
2 + 2
Motor Rating
kW
24.0 / 24.0
24.0 / 24.0
28.2 / 24.0
Sump Heater Rating
W
75
75
130 + 75
Start Amps (2)
A
260 / 260
260 / 260
320 / 260
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
36.5
42.8
Circuit 2 Comp RLA (PFC)
36.5
36.5
36.5
Nominal Run Amps
A
160.9
165.9
173.5
Maximum Start Amps
A
384.5
389.5
450.8
Compressor Nominal Run Amps
A
36.5 / 36.5
36.5 / 36.5
42.8 / 36.5
Recommended Mains Fuse Size
A
250
250
250
Electronic Soft-start
Nominal Run Amps
A
187.2
192.2
196.1
Maximum Start Amps
A
300.2
305.2
340.6
Recommended Mains Fuse
A
250
250
250
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
160.9
165.9
173.5
Maximum Start Amps
A
280.5
285.5
322.8
Compressor Nominal Run Amps
A
36.5 / 36.5
36.5 / 36.5
42.8 / 36.5
Recommended Mains Fuse Size
A
250
250
250
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.2
6.2
6.2
Unit Nominal Run Amps
A
193.4
198.4
202.3
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
3
3
3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
196.1
201.1
205.0
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
4
4
4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.0
8.0
11.2
Unit Nominal Run Amps
A
195.2
200.2
207.3
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
4
4
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
198.4
203.4
207.3
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
5.5
5.5
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.