Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 77
![background image](/manuals/370932/77/background.png)
Chillers
DELTACHILL
™
Chillers
77
Installation, Commissioning and Maintenance Manual :7025232 12/ 2013
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF023DR-06BKK0
6
236.0
61.4
223.6
67.0
210.5
73.2
196.6
80.2
7
243.2
61.7
230.5
67.3
217.0
73.5
202.7
80.5
8
250.5
62.1
237.5
67.6
223.7
73.9
209.0
80.9
10
265.5
62.8
251.8
68.4
237.3
74.6
221.8
81.6
12
281.0
63.6
266.6
69.2
251.3
75.4
235.1
82.4
14
296.8
64.5
281.7
70.0
265.7
76.2
248.7
83.2
DCF026DR-06BKL0
6
267.1
72.1
252.7
78.3
237.4
85.3
220.8
93.1
7
275.2
72.5
260.4
78.8
244.6
85.8
227.7
93.5
8
283.4
72.9
268.3
79.2
252.0
86.2
234.6
94.0
10
300.2
73.8
284.2
80.1
267.1
87.1
248.8
94.9
12
317.4
74.8
300.6
81.1
282.7
88.1
263.4
95.9
14
335.1
75.8
317.5
82.1
298.6
89.1
278.4
96.9
DCF029DR-06BLL0
6
292.9
82.5
277.1
89.5
260.0
97.2
241.4
105.8
7
301.7
83.0
285.5
90.0
267.8
97.7
248.7
106.3
8
310.6
83.5
293.9
90.5
275.8
98.3
256.1
106.9
10
328.8
84.5
311.2
91.6
292.1
99.4
271.4
108.0
12
347.5
85.6
328.9
92.7
308.8
100.5
287.0
109.2
14
366.6
86.7
347.0
93.8
325.9
101.7
303.0
110.4
DCF032DR-08BLM0
6
328.7
88.4
311.7
95.7
293.3
103.7
273.4
112.6
7
338.7
88.9
321.2
96.2
302.3
104.3
281.9
113.2
8
348.9
89.4
330.9
96.7
311.5
104.8
290.5
113.7
10
369.7
90.4
350.7
97.8
330.2
105.9
308.0
114.8
12
391.1
91.4
371.1
98.8
349.5
107.0
326.1
116.0
14
413.0
92.4
392.0
99.9
369.2
108.1
344.7
117.2
DCF035DR-08BMM0
6
350.7
95.3
332.2
103.2
312.3
111.9
290.9
121.5
7
361.3
95.8
342.2
103.8
321.8
112.5
299.8
122.2
8
372.0
96.4
352.4
104.5
331.4
113.2
308.8
122.8
10
393.9
97.7
373.2
105.7
351.0
114.5
327.1
124.2
12
416.3
98.9
394.5
107.1
371.1
115.9
346.0
125.7
14
439.4
100.2
416.4
108.4
391.8
117.3
365.4
127.1
DCF039DR-10BMS0
6
405.2
109.1
384.1
118.1
361.3
128.1
336.7
139.0
7
417.5
109.7
395.9
118.7
372.5
128.7
347.2
139.7
8
430.1
110.2
407.9
119.4
383.8
129.3
357.8
140.3
10
455.8
111.4
432.3
120.6
407.0
130.6
379.5
141.7
12
482.3
112.7
457.5
121.9
430.8
132.0
401.9
143.1
14
509.4
113.9
483.4
123.2
455.2
133.4
424.9
144.5
DCF044DR-10BSS0
6
444.9
123.0
421.4
133.3
396.0
144.7
368.4
157.3
7
458.4
123.6
434.3
134.0
408.1
145.4
379.7
158.1
8
472.1
124.3
447.4
134.7
420.5
146.1
391.3
158.8
10
500.2
125.7
474.0
136.1
445.7
147.6
414.9
160.4
12
529.0
127.1
501.4
137.6
471.6
149.2
439.2
161.9
14
558.5
128.6
529.5
139.1
498.1
150.7
464.2
163.6
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.