Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Code

Description

Auto Reset (Yes/No)

Unit Disabled

(Yes/No)

Component

Disabled
(Yes/No)

Cause

Action

AL055

Hours
Limit Pump
1

Yes

No

No

The hours run for the pump has

exceeded the threshold

If component is

functioning

correctly perform

maintenance and

reset hours

AL056

Hours
Limit Pump
2

AL057

CW Valve
Feedback

Yes

Yes

Yes

Valve Failed to open

Check: Valve

operation / Wiring

AL058

Low
Suction
Pressure 1

Yes

No

Yes

The suction pressure has

exceeded the low limit during

operation

Check: Evaporator

flow rate / Unit TD /

Refrigerant charge

AL059

Low
Suction
Pressure 2

AL060

pLAN
Network
Alarm

Yes

No

No

Chiller controller has lost

communication with sequence

controller

Check: Wiring /

pLan Connection /

Address

AL061

Oil Pre-
Heat Delay

Yes

Yes

Yes

Follows a controller power

restart and indicates time delay

before compressors restart

No action

necessary

AL062

Cct1 Diff.
Pressure

Yes

No

Yes

The compressor differential

pressure limits have been

exceeded

Check: Evaporator

flow rate / Unit TD /

Refrigerant charge

AL063

Cct2 Diff.
Pressure

AL064

Possible
Leak Unit

Yes

No

No

The reading from the leak

detector is above the threshold

Check: Pipe work

around the leak

detector

AL065

Evap.Inlet
Temp.
Fault

Yes

Yes

Yes

The Sensor has gone out of its

operating range

Check: Wiring /

Sensor

AL066

Circuit 1
Disabled
After
Pumpdown

No

No

Yes

The circuit has been pumped

down following a possible
refrigerant leak or manual

pumpdown request and

disabled

Investigate reason

for pumpdown and

reset

AL067

Circuit 2
Disabled
After
Pumpdown