Unit alarms, Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 163
![background image](/manuals/370932/163/background.png)
Chillers
DELTACHILL
™
Chillers
163
Installation, Commissioning and Maintenance Manual :7025232 12/ 2013
Unit Alarms
Code
Description
Auto
Reset
(Yes/No)
Unit Disabled
(Yes/No)
Component
Disabled (Yes/No)
Cause
Action
AL001
Power Meter MB Offline
Yes
Yes
Yes
Communication to the
Power Meter has been lost
Check: Wiring /
Modbus card /
Power Meter
AL002
EVD1 pLAN Offline
Yes
No
Yes
Communication to the EVD
Driver has been lost
Check: Wiring /
pLan Connection /
Address
AL003
EVD2 pLAN Offline
AL004
Cond. Pressure1 Fault
Yes
No
Yes
The Sensor has gone out of
its operating range
Check: Wiring /
Sensor
AL005
Cond. Pressure2 Fault
No
AL006
Evap.Diff.Press. Fault
Yes
AL007
Return Temp. Fault
AL008
Supply Temp. Fault
Yes
AL009
Temp. Setpoint Fault
No
AL010
Cond.Air On Temp Fault
No
AL011
Clock Alarm
Yes
No
Yes
The internal clock has
malfunctioned
Replace Battery
AL012
Emergency Stop
Yes
Yes
Yes
The emergency stop button
has been pressed
Release the
emergency stop
button
AL013
Phase Failure
Yes
Yes
Yes
The 3 phase power supply
crossed / loss (wait 30s with
a power meter on power up)
Check 3 phase
connection
AL014
Evaporator Flow Alarm
Yes
Yes
Yes
No water flow has been
detected
Check: pumps are
running / flow
sensor
AL015
Low Pressure 1 Switch
Yes
No
Yes
The pressure in the system
is below 0.5 bar
Check: Refrigerant
charge / EEV
operation
AL016
Low Pressure 2 Switch
AL017
Cct1 Comp1 Status Al.
Yes
No
Yes
Contactor has been
switched on but has failed to
operate
Check: High
Pressure Switch /
contactor. / Wiring.
AL018
Cct1 Comp2 Status Al.
AL019
Cct1 Comp3 Status Al.
AL020
Cct2 Comp1 Status Al.
AL021
Cct2 Comp2 Status Al.
AL022
Cct2 Comp3 Status Al.
AL023
Pump1 Status Alarm
Yes
Yes
Contactor has been
switched on but has failed to
operate
Check: High
Pressure Switch /
contactor. / Wiring.
AL024
Pump2 Status Alarm
AL025
Low Supply Temperature
Yes
Yes
Yes
The supply water
temperature is too low
Check: Flow Rate /
Unit TD
AL026
High Cond. Pressure 1
Yes
No
Yes
The condensing pressure is
higher than 40.0Bar
Check: Condenser
/ Condenser Fans
AL027
High Cond. Pressure 2
AL028
pCOe Module Offline
Yes
No
Yes
Communication to the pCOe
expansion module has been
lost
Check:
Communications
link / Wiring
AL029
S1 Probe Fault EVD1
No
Yes
The Evaporator pressure
probe is out of range
Check: Pressure
probe / Wiring