Chillers

DELTACHILL

Chillers

111

Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Free Cool Chiller Extra Quiet Continued

ELECTRICAL DATA

DCF023DX-06BKK0

DCF026DX-08BKL0

DCF029DX-08BLL0

Unit Data

Nominal Run Amps

(1)

A

147.1

172.2

192.2

Maximum Start Amps

A

329.1

389.1

409.2

Recommended Mains Fuse Size

A

160

200

250

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

6

8

8

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

6

8

8

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0 / 33.0

33.0 / 43.1

43.1 / 43.1

Quantity

2 + 2

2 + 2

2 + 2

Motor Rating

kW

18.8 / 18.8

18.8 / 24.0

24.0 / 24.0

Sump Heater Rating

W

75

75

75

Start Amps

A

215 / 215

215 / 260

260 / 260

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

28.5

36.5

Circuit 2 Comp RLA (PFC)

28.5

36.5

36.5

Nominal Run Amps

A

129.0

150.0

165.9

Maximum Start Amps

A

315.5

373.5

389.5

Compressor Nominal Run Amps

A

28.5 / 28.5

28.5 / 36.5

36.5 / 36.5

Recommended Mains Fuse Size

A

160

200

250

Electronic Soft-start

Nominal Run Amps

A

147.1

172.2

192.2

Maximum Start Amps

A

243.1

285.1

305.2

Recommended Mains Fuse

A

160.0

200.0

250.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

129.0

150.0

165.9

Maximum Start Amps

A

229.5

269.5

285.5

Compressor Nominal Run Amps

A

28.5 / 28.5

28.5 / 36.5

36.5 / 36.5

Recommended Mains Fuse Size

A

160

200

250

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

N/A

N/A

N/A

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

12

12

Unit Nominal Run Amps

A

156.0

184.2

204.2

Recommended Mains Fuse Size

A

200

250

250

Motor Rating

kW

4

5.5

5.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.8

11.8

14

Unit Nominal Run Amps

A

158.9

184.0

206.2

Recommended Mains Fuse Size

A

200

200

250

Motor Rating

kW

5.5

5.5

7.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8

11.2

11.2

Unit Nominal Run Amps

A

155.1

183.4

203.4

Recommended Mains Fuse Size

A

200

250

250

Motor Rating

kW

4

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

14.8

14.8

Unit Nominal Run Amps

A

158.3

187.0

207.0

Recommended Mains Fuse Size

A

200

200

250

Motor Rating

kW

5.5

7.5

7.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.