Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 79
Chillers
DELTACHILL
™
Chillers
79
Installation, Commissioning and Maintenance Manual :7025232 12/ 2013
Mechanical Cooling Performance AC Fans Extra Quiet
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF013DX-04ACD0
6
135.9
34.7
128.8
37.7
121.1
41.2
112.8
45.0
7
140.1
34.9
132.8
37.9
124.9
41.4
116.4
45.2
8
144.4
35.1
136.9
38.1
128.7
41.6
120.0
45.4
10
153.1
35.5
145.1
38.6
136.6
42.0
127.3
45.9
12
162.0
35.9
153.6
39.0
144.6
42.5
134.9
46.3
14
171.2
36.4
162.3
39.5
152.9
42.9
142.7
46.8
DCF014DX-04ADD0
6
149.4
39.7
141.6
43.1
133.0
46.9
123.7
51.1
7
154.0
39.9
145.9
43.3
137.1
47.2
127.5
51.4
8
158.6
40.1
150.3
43.6
141.3
47.4
131.4
51.6
10
168.0
40.6
159.3
44.1
149.7
47.9
139.3
52.2
12
177.7
41.1
168.5
44.6
158.4
48.4
147.5
52.7
14
187.7
41.6
177.9
45.1
167.3
49.0
155.9
53.3
DCF015DX-04ADF0
6
161.7
43.7
152.8
47.4
143.3
51.6
132.9
56.2
7
166.5
44.0
157.4
47.7
147.6
51.9
136.9
56.6
8
171.5
44.2
162.1
48.0
152.0
52.2
141.0
56.9
10
181.5
44.9
171.6
48.7
160.9
52.9
149.3
57.6
12
191.8
45.5
181.4
49.3
170.1
53.6
157.9
58.3
14
202.3
46.1
191.3
50.0
179.4
54.3
166.7
59.0
DCF016DX-04AJJ0
6
167.4
45.7
158.0
49.9
147.9
54.5
137.2
59.7
7
172.6
46.0
162.9
50.2
152.6
54.8
141.5
60.0
8
177.8
46.3
167.8
50.5
157.2
55.1
145.8
60.3
10
188.4
46.9
178.0
51.1
166.7
55.8
154.7
61.0
12
199.4
47.6
188.3
51.9
176.5
56.6
163.8
61.8
14
210.5
48.3
198.9
52.6
186.4
57.3
173.1
62.6
DCF018DX-04BJK0
6
191.7
55.6
180.4
60.9
168.3
66.9
155.3
73.5
7
197.3
56.1
185.7
61.4
173.3
67.3
160.0
74.0
8
202.9
56.6
191.1
61.9
178.2
67.9
164.7
74.5
10
214.6
57.5
202.0
62.9
188.6
68.9
174.2
75.5
12
226.5
58.5
213.2
63.9
199.1
69.9
183.9
76.6
14
238.6
59.5
224.6
65.0
209.8
71.0
193.9
77.8
DCF020DX-06BFK0
6
206.4
53.3
195.4
58.1
183.7
63.5
171.1
69.5
7
212.7
53.6
201.4
58.4
189.3
63.8
176.4
69.9
8
219.0
53.9
207.5
58.8
195.1
64.2
181.8
70.2
10
232.0
54.6
219.8
59.5
206.8
64.9
192.7
71.0
12
245.4
55.3
232.6
60.2
218.8
65.7
204.0
71.8
14
259.1
56.1
245.6
61.0
231.2
66.5
215.7
72.6
DCF023DX-06BKK0
6
230.6
60.4
218.0
66.2
204.6
72.8
190.3
80.1
7
237.5
60.8
224.6
66.6
210.9
73.2
196.2
80.5
8
244.6
61.2
231.3
67.0
217.2
73.6
202.1
80.9
10
258.9
62.1
245.0
67.9
230.1
74.5
214.2
81.8
12
273.7
63.0
259.0
68.8
243.4
75.4
226.7
82.8
14
288.8
64.0
273.4
69.8
257.0
76.4
239.5
83.8
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.