Unit Alarm Interrogation


Alarm Menu Display











Alarm Log

The alarm page offers a log of the last 150 alarm messages in a scrolling log, pressing the alarm button will enter the
alarm page. Consequently the most recent alarm has the lowest log number (001) and will be displayed upon entering
the alarm page. As another alarm occurs, the alarm number increases until 150 alarms have occurred. From this point
on, alarm 001 moves to 002 and any new alarm will reside in position 001. As new alarms are generated and cleared,
the highest number logs (150) in the scroll will be lost.


Viewing the Alarm Log

By using the arrow keys, the last 150 alarms generated can be reviewed in chronological order. The display provides the
alarm type information and the time and date of each alarm occurrence.


Alarm Detection

When the controller detects an alarm an output is generated to the relevant alarm relay which in turn illuminates the

button. To see which alarm has accrued press the

button and the most recent alarm will be displayed. If the alarm

light is on, the alarm page can be interrogated to identify which alarm is active.


Resetting the Alarm

The auto reset alarms will automatically reset once the conditions are within the set parameters. To clear a manual alarm

press the

button twice and the red LED will disappear.



Erasing the Alarm Log

The alarm history log can be erased by selecting Erase Alarm Log in Manufacturer Parameters.

Alarm Status

Time

Unit Demand
Return Temp

Alarm Number

Alarm Name

Date

Ambient
Supply Temp