DELTACHILL
™
Chillers
156
Chillers
Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013
Item
Task
Frequency
Waterside
3 Mths
12 Mths
60 Mths
Check pressure drop of water strainer. If excessive clean
the strainer.
Visually inspect pipe and pipework insulation. Pipework
clamps are secure.
Inspect for water leakage
Check pressure drop of evaporator. Clean evaporator if
excessive.
Check condition of Water/ Glycol solution to ensure that the
system is protected against corrosion, scale and
microbiological fouling, ensuring maximum heat transfer
efficiency.
The evaporator is constructed from ?
Care must be taken in selecting cleaning solutions.
Only approved chemicals must be used.
System
Check the following against the commissioning records.
Record operating conditions.
Water on/ off temperatures
Water pressure drop
Service tools / Test Equipment
Spanners
Manometer
Thermometer
Safety Equipment
Safety glasses/ goggles
Gloves
Overalls