Waterside, Deltachill ™ chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 156

Advertising
background image

DELTACHILL

Chillers

156

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Item

Task

Frequency

Waterside

3 Mths

12 Mths

60 Mths

Check pressure drop of water strainer. If excessive clean
the strainer.

Visually inspect pipe and pipework insulation. Pipework
clamps are secure.

Inspect for water leakage

Check pressure drop of evaporator. Clean evaporator if
excessive.

Check condition of Water/ Glycol solution to ensure that the
system is protected against corrosion, scale and
microbiological fouling, ensuring maximum heat transfer
efficiency.

The evaporator is constructed from ?

Care must be taken in selecting cleaning solutions.

Only approved chemicals must be used.

System

Check the following against the commissioning records.

Record operating conditions.

Water on/ off temperatures

Water pressure drop





Service tools / Test Equipment

Spanners

Manometer

Thermometer

Safety Equipment

Safety glasses/ goggles

Gloves

Overalls