Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Commissioning Procedure

Electrical

Electrical
connections

Ensure all electrical connections are tight and correctly terminated.

External fuses/
MCB’s

Check that the correct electrical supply rating is available to the unit

Electrical continuity

Before electrical power is applied to the unit. Electrical continuity checks must be carried
out on the 3 phase power.

Phase rotation

Check that the electrical phase rotation is correct. Components in the unit may
malfunction with incorrect phase rotation.

Electrical earthing

Check that the unit is correctly earthed.

Remote on/off

To ensure that the unit does not start whist doing the pre-commissioning checks the
remote on/off should be in the OFF state.

Voltage

Measure the voltage at the following points and record on the commissioning sheet

Voltage at busbar

Dedicated power supply

Voltage at permanent supply

Control voltage at transformer (min 22.5V, max 25V)


The vo

ltage measurements should be carried out with the unit MCB’s turned off.