Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 57

Advertising
background image

Chillers

DELTACHILL

Chillers

57

Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Regular Quiet Continued

ELECTRICAL DATA

DCC031DR-08BLM0

DCC032DR-06BMM0

DCC033DR-08BMM0

Unit Data

Nominal Run Amps

(1)

A

215.5

215.8

224.4

Maximum Start Amps

(2)

A

488.0

488.3

496.9

Recommended Mains Fuse Size

A

250

250

250

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

8

6

8

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

8

6

8

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 43.1

47.5 / 47.5

47.5 / 47.5

Quantity

2 + 2

2 + 2

2 + 2

Motor Rating

kW

28.2 / 24.0

28.2 / 28.2

28.2 / 28.2

Sump Heater Rating

W

130 + 75

130

130

Start Amps (2)

A

320 / 260

320 / 260

320 / 320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

42.8

42.8

Circuit 2 Comp RLA (PFC)

36.5

42.8

42.8

Nominal Run Amps

A

192.9

196.9

205.5

Maximum Start Amps

A

470.2

414.2

482.8

Compressor Nominal Run Amps

A

42.8 / 36.5

42.8 / 42.8

42.8 / 42.8

Recommended Mains Fuse Size

A

250

250

250

Electronic Soft-start

Nominal Run Amps

A

215.5

215.8

224.4

Maximum Start Amps

A

360.0

360.3

368.9

Recommended Mains Fuse

A

250

250

250

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

192.9

196.9

205.5

Maximum Start Amps

A

342.2

310.2

354.8

Compressor Nominal Run Amps

A

42.8 / 36.5

42.8 / 42.8

42.8 / 42.8

Recommended Mains Fuse Size

A

250

250

250

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.2

8.9

8.9

Unit Nominal Run Amps

A

221.7

224.66

233.26

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

3

4

4

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

12

12

Unit Nominal Run Amps

A

224.4

227.76

236.36

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

4

5.5

5.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

226.7

227.0

235.6

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

5.5

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

226.7

226.96

235.56

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

5.5

5.5

5.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.