Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 83

Advertising
background image

Chillers

DELTACHILL

Chillers

83

Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF026DR-06BKL0

6

264.1

70.1

250.7

76.8

236.5

84.2

221.4

92.6

7

272.3

70.6

258.5

77.3

244.0

84.8

228.6

93.1

8

280.6

71.1

266.5

77.8

251.6

85.3

235.7

93.6

10

297.5

72.2

282.9

78.9

267.3

86.4

250.3

94.6

12

315.1

73.3

299.8

80.0

283.5

87.6

265.2

95.6

14

333.2

74.5

317.1

81.2

300.0

88.7

280.7

96.7

DCF029DR-06BLL0

6

291.2

81.4

276.6

88.8

261.0

97.0

244.3

106.2

7

300.2

81.9

285.2

89.4

269.2

97.6

252.2

106.8

8

309.3

82.5

293.9

90.0

277.6

98.3

259.9

107.4

10

328.1

83.7

312.0

91.2

294.8

99.6

275.6

108.5

12

347.4

85.0

330.5

92.5

312.6

100.9

291.6

109.6

14

367.3

86.3

349.7

93.8

330.7

102.1

308.1

110.7

DCF032DR-08BLM0

6

323.5

84.8

307.3

92.6

290.0

101.2

271.4

110.8

7

333.5

85.4

316.9

93.2

299.1

101.8

280.1

111.4

8

343.7

86.0

326.6

93.8

308.4

102.5

288.9

112.1

10

364.5

87.3

346.6

95.2

327.4

103.8

307.0

113.5

12

386.1

88.6

367.2

96.5

347.1

105.2

325.7

115.0

14

408.2

89.9

388.8

98.0

367.4

106.7

345.0

116.4

DCF035DR-08BMM0

6

346.1

92.4

328.6

100.8

310.0

110.1

290.3

120.5

7

356.7

93.1

338.7

101.6

319.6

110.9

299.5

121.3

8

367.5

93.9

349.0

102.3

329.5

111.7

308.7

122.1

10

389.7

95.4

370.2

103.9

349.7

113.3

327.9

123.8

12

412.5

96.9

392.1

105.5

370.5

115.0

347.7

125.5

14

436.1

98.5

414.6

107.1

392.1

116.7

368.3

127.2

DCF039DR-10BMS0

6

398.6

104.4

378.6

114.0

357.2

124.6

334.3

136.4

7

411.0

105.1

390.5

114.8

368.5

125.4

345.0

137.3

8

423.6

105.9

402.5

115.6

379.9

126.2

355.9

138.1

10

449.4

107.4

427.2

117.1

403.5

127.9

378.2

139.8

12

476.0

109.0

452.7

118.8

427.8

129.5

401.4

141.5

14

503.4

110.6

478.9

120.4

452.9

131.3

425.3

143.3

DCF044DR-10BSS0

6

439.6

119.7

417.6

130.7

393.9

142.9

368.7

156.5

7

453.2

120.5

430.7

131.6

406.4

143.8

380.5

157.4

8

467.1

121.4

443.9

132.4

419.1

144.7

392.6

158.3

10

495.5

123.1

471.1

134.2

445.1

146.5

417.3

160.2

12

524.8

124.8

499.3

136.0

472.0

148.4

443.0

162.2

14

555.0

126.6

528.2

137.8

499.8

150.3

469.5

164.1

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.