Mechanical Cooling EC Fans Regular Quiet

Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF014SR-04AL00

6

149.2

38.5

141.9

42.1

134.0

46.1

125.4

50.5

7

153.9

38.8

146.4

42.3

138.2

46.3

129.5

50.7

8

158.7

39.0

150.9

42.6

142.6

46.6

133.6

51.0

10

168.4

39.5

160.3

43.1

151.5

47.1

142.0

51.6

12

178.5

40.1

169.9

43.7

160.7

47.7

150.8

52.2

14

188.8

40.6

179.9

44.2

170.2

48.3

159.9

52.7

DCF017SR-04AM00

6

174.2

46.3

165.3

50.5

156.0

55.1

146.0

60.3

7

179.6

46.7

170.5

50.9

160.8

55.5

150.6

60.7

8

185.1

47.0

175.7

51.3

165.8

55.9

155.4

61.1

10

196.3

47.8

186.4

52.1

176.0

56.7

165.0

62.0

12

207.8

48.6

197.5

52.9

186.6

57.6

175.1

62.8

14

219.8

49.4

208.9

53.7

197.5

58.5

185.4

63.7

DCF021SR-04BS00

6

213.8

62.5

203.0

68.2

191.1

74.3

177.4

80.7

7

220.4

63.0

209.3

68.7

196.9

74.7

182.7

81.2

8

227.0

63.5

215.8

69.2

202.7

75.1

188.2

81.6

10

240.8

64.4

228.7

70.1

214.6

76.0

199.3

82.5

12

254.9

65.4

241.6

70.9

226.8

76.9

210.7

83.4

14

269.4

66.4

254.9

71.8

239.3

77.8

222.4

84.3

DCF025SR-06BT00

6

256.7

70.2

243.5

76.6

229.4

83.7

214.6

91.6

7

264.6

70.8

251.0

77.2

236.6

84.3

221.4

92.2

8

272.6

71.3

258.6

77.8

243.9

84.9

228.3

92.8

10

289.0

72.4

274.3

78.9

258.8

86.1

242.4

94.1

12

306.0

73.6

290.6

80.2

274.3

87.3

257.1

95.4

14

323.4

74.8

307.3

81.4

290.2

88.6

272.3

96.7



1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.

Advertising