Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Free Cool Chiller Extra Quiet Continued

ELECTRICAL DATA

DCF039DX-10BMS0

DCF044DX-12BSS0

Unit Data

Nominal Run Amps

(1)

A

249.2

288.4

Maximum Start Amps

A

521.7

505.3

Recommended Mains Fuse Size

A

315

315

Mains Supply

VAC

Max Mains Incoming Cable Size

mm²

Recommended Permanent Fuse Size

A

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

External Trace Heating

Available (fitted by others)

W

500

500

Condenser Fan - Per Fan (AC)

Quantity

10

12

Full Load Amps

A

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

Motor Rating

kW

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

10

12

Full Load Amps

A

3.4

3.4

Locked Rotor Amps

A

N/A

N/A

Motor Rating

kW

2.2

2.2

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 43.1

43.1 / 43.1

Quantity

2 + 3

3 + 3

Motor Rating

kW

28.2 / 24.0

24.0 / 24.0

Sump Heater Rating

W

130 + 75

75

Start Amps

A

320 / 260

260 / 260

Type Of Start

Direct on line

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

36.5

Circuit 2 Comp RLA (PFC)

36.5

36.5

Nominal Run Amps

A

220.0

248.9

Maximum Start Amps

A

497.2

472.4

Compressor Nominal Run Amps

A

42.8 / 36.5

36.5 / 36.5

Recommended Mains Fuse Size

A

315

315

Electronic Soft-start

Nominal Run Amps

A

249.2

288.4

Maximum Start Amps

A

393.7

401.3

Recommended Mains Fuse

A

315.0

315.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

220.0

248.9

Maximum Start Amps

A

369.2

368.4

Compressor Nominal Run Amps

A

42.8 / 36.5

36.5 / 36.5

Recommended Mains Fuse Size

A

315

315

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

N/A

N/A

Full Load Amps

A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

Motor Rating

kW

N/A

N/A

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

14

14

Unit Nominal Run Amps

A

263.2

302.4

Recommended Mains Fuse Size

A

315

355

Motor Rating

kW

7.5

7.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

20.8

20.8

Unit Nominal Run Amps

A

270.0

309.2

Recommended Mains Fuse Size

A

315

355

Motor Rating

kW

11

11

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

14.8

14.8

Unit Nominal Run Amps

A

264.0

303.2

Recommended Mains Fuse Size

A

315

355

Motor Rating

kW

7.5

7.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

21.2

21.2

Unit Nominal Run Amps

A

270.4

309.6

Recommended Mains Fuse Size

A

315

355

Motor Rating

kW

11

11

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.