Commissioning Procedure

Refrigeration

Compressor

Record on the commissioning sheet compressor details

Type

Serial numbers

Overload settings

Condenser fans

Record on commissioning sheets condenser fan details

Type

Size (kW)

Serial number

Controller type

Running currents


The condenser fans can be operated manually through the controller ensuring correct
operation before the refrigeration circuit is energised.

Check rotation

Operating conditions

Record the following operating conditions of the unit at stable conditions.

Suction pressure (bar)

Liquid pressure (Bar)

Discharge pressure (Bar)

Suction temperature (°C)

Liquid temperature (°C)

Discharge temperature (°C)

Superheat (°C)

Sub cooling (°C)

Water return temperature (°C)

Water supply temperature (°C)


Liquid line sight
glass

Record the status of the liquid line sight glass

Clear/ flashing

Wet/dry

The sight glass is used to indicate

the condition of the refrigerant in the system

lack of sub-cooling

refrigerant deficiency

Moisture content of the refrigerant


The colour of the sight glass depends on the moisture content of the refrigerant. The
recommended moisture levels of a system should be between 30 and 75ppm.
An indication of green/dry are to be considered as perfect conditions meaning full
protection by the filter drier against effects from moisture.

If the green colour starts to fade, the colour change from green to yellow has begun and
the indicator should therefore be watched carefully. If the colour changes to yellow it is a
clear signal that the capacity of the filer drier is exceeded and should be replaced as
soon as possible.