Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 68
DELTACHILL
™
Chillers
68
Chillers
Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013
Electrical Data Extra Quiet Continued
ELECTRICAL DATA
DCC031DX-08BLM0
DCC032DX-06BMM0
DCC033DX-08BMM0
Unit Data
Nominal Run Amps
(1)
A
196.1
205.0
210.0
Maximum Start Amps
(2)
A
468.6
477.5
482.5
Recommended Mains Fuse Size
A
250
250
250
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
6
6
8
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
6
6
8
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 43.1
47.5 / 47.5
47.5 / 47.5
Quantity
2 + 2
2 + 2
2 + 2
Motor Rating
kW
28.2 / 24.0
28.2 / 28.2
28.2 / 28.2
Sump Heater Rating
W
130 + 75
130
130
Start Amps (2)
A
320 / 260
320 / 260
320 / 320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
42.8
42.8
42.8
Circuit 2 Comp RLA (PFC)
36.5
42.8
42.8
Nominal Run Amps
A
173.5
186.1
191.1
Maximum Start Amps
A
450.8
463.4
468.4
Compressor Nominal Run Amps
A
42.8 / 36.5
42.8 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
250
Electronic Soft-start
Nominal Run Amps
A
196.1
205.0
210.0
Maximum Start Amps
A
340.6
349.5
354.5
Recommended Mains Fuse
A
250
250
250
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
173.5
186.1
191.1
Maximum Start Amps
A
322.8
335.4
340.4
Compressor Nominal Run Amps
A
42.8 / 36.5
42.8 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
250
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.2
6.2
6.2
Unit Nominal Run Amps
A
202.3
211.2
216.2
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
3
3
3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
205
213.86
218.86
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
4
4
4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
207.3
216.2
221.2
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
5.5
5.5
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
207.3
216.2
221.2
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
5.5
5.5
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.