Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 68

Advertising
background image

DELTACHILL

Chillers

68

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC031DX-08BLM0

DCC032DX-06BMM0

DCC033DX-08BMM0

Unit Data

Nominal Run Amps

(1)

A

196.1

205.0

210.0

Maximum Start Amps

(2)

A

468.6

477.5

482.5

Recommended Mains Fuse Size

A

250

250

250

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

6

6

8

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

6

6

8

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 43.1

47.5 / 47.5

47.5 / 47.5

Quantity

2 + 2

2 + 2

2 + 2

Motor Rating

kW

28.2 / 24.0

28.2 / 28.2

28.2 / 28.2

Sump Heater Rating

W

130 + 75

130

130

Start Amps (2)

A

320 / 260

320 / 260

320 / 320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

42.8

42.8

Circuit 2 Comp RLA (PFC)

36.5

42.8

42.8

Nominal Run Amps

A

173.5

186.1

191.1

Maximum Start Amps

A

450.8

463.4

468.4

Compressor Nominal Run Amps

A

42.8 / 36.5

42.8 / 42.8

42.8 / 42.8

Recommended Mains Fuse Size

A

250

250

250

Electronic Soft-start

Nominal Run Amps

A

196.1

205.0

210.0

Maximum Start Amps

A

340.6

349.5

354.5

Recommended Mains Fuse

A

250

250

250

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

173.5

186.1

191.1

Maximum Start Amps

A

322.8

335.4

340.4

Compressor Nominal Run Amps

A

42.8 / 36.5

42.8 / 42.8

42.8 / 42.8

Recommended Mains Fuse Size

A

250

250

250

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.2

6.2

6.2

Unit Nominal Run Amps

A

202.3

211.2

216.2

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

3

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

205

213.86

218.86

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

4

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

207.3

216.2

221.2

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

5.5

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

207.3

216.2

221.2

Recommended Mains Fuse Size

A

250

250

250

Motor Rating

kW

5.5

5.5

5.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.